{"id":21474,"date":"2026-01-28T18:23:42","date_gmt":"2026-01-28T10:23:42","guid":{"rendered":"https:\/\/viox.com\/?p=21474"},"modified":"2026-01-28T18:23:46","modified_gmt":"2026-01-28T10:23:46","slug":"mccb-short-time-delay-icw-rating-explained","status":"publish","type":"post","link":"https:\/\/test.viox.com\/fr\/mccb-short-time-delay-icw-rating-explained\/","title":{"rendered":"Pourquoi les MCCB offrent-ils une protection \u00e0 court retard sans courant admissible de court retard nominal (I<sub>cw<\/sub>)"},"content":{"rendered":"<div class=\"product-intro\">\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/MCCB-electronic-trip-unit-in-industrial-panel-showing-400A-rating-and-current-display.webp\" alt=\"MCCB electronic trip unit in industrial panel showing 400A rating and current display - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">D\u00e9clencheur \u00e9lectronique MCCB dans un panneau industriel affichant un calibre de 400 A et un affichage du courant \u2013 VIOX Electric<\/figcaption><\/figure>\n<h2>R\u00e9ponse directe<\/h2>\n<p><strong><a href=\"https:\/\/test.viox.com\/fr\/mccb\/\">Disjoncteurs \u00e0 bo\u00eetier moul\u00e9 (MCCB)<\/a> peut fournir une protection contre les courts retards sans courant admissible de court-circuit nominal (I<sub>cw<\/sub>) car ils appartiennent \u00e0 la cat\u00e9gorie A de la norme CEI 60947-2, o\u00f9 la s\u00e9lectivit\u00e9 est obtenue gr\u00e2ce \u00e0 une technologie de limitation de courant plut\u00f4t qu'\u00e0 des temporisations intentionnelles.<\/strong> Contrairement aux disjoncteurs de puissance (ACB) de cat\u00e9gorie B qui \u201c attendent \u201d les courants de d\u00e9faut en utilisant un I<sub>cw<\/sub> \u00e9lev\u00e9, les MCCB utilisent la r\u00e9pulsion \u00e9lectromagn\u00e9tique des contacts et la coupure d'arc ultra-rapide pour limiter l'\u00e9nergie de d\u00e9faut, se prot\u00e9geant ainsi tout en se coordonnant avec les appareils en aval gr\u00e2ce \u00e0 leurs caract\u00e9ristiques de court d\u00e9lai inh\u00e9rentes (g\u00e9n\u00e9ralement 10 \u00e0 12 \u00d7 I<sub>n<\/sub>) en dessous du seuil de d\u00e9clenchement instantan\u00e9.<\/p>\n<hr \/>\n<h2>Principaux enseignements<\/h2>\n<ul>\n<li>\u2705 <strong>Cat\u00e9gorie A vs. B<\/strong>: Les MCCB (cat\u00e9gorie A) n'ont pas de I<sub>cw<\/sub> d\u00e9clar\u00e9es, mais poss\u00e8dent une capacit\u00e9 de tenue aux courts retards inh\u00e9rente en dessous de leur seuil de r\u00e9pulsion des contacts (g\u00e9n\u00e9ralement &gt; 12-14 \u00d7 I<sub>n<\/sub>)<\/li>\n<li>\u2705 <strong>Physique de la limitation de courant<\/strong>: La pression du ressort de contact est intentionnellement faible dans les MCCB pour permettre une r\u00e9pulsion \u00e9lectromagn\u00e9tique rapide en cas de courants de d\u00e9faut \u00e9lev\u00e9s (&gt; 25 \u00d7 I<sub>n<\/sub>), \u00e9vitant ainsi les dommages gr\u00e2ce \u00e0 une interruption rapide plut\u00f4t qu'\u00e0 une tenue prolong\u00e9e<\/li>\n<li>\u2705 <strong>R\u00e9alit\u00e9 du court d\u00e9lai<\/strong>: Les r\u00e9glages de court d\u00e9lai des MCCB (par exemple, 10 \u00d7 I<sub>n<\/sub>, 0,4 s) ne fonctionnent que lorsque le courant de d\u00e9faut reste inf\u00e9rieur au seuil de d\u00e9clenchement instantan\u00e9 - le d\u00e9passement de ce seuil d\u00e9clenche une action imm\u00e9diate via un d\u00e9clenchement magn\u00e9tique ou des m\u00e9canismes bas\u00e9s sur l'\u00e9nergie<\/li>\n<li>\u2705 <strong>Limites de s\u00e9lectivit\u00e9<\/strong>: La s\u00e9lectivit\u00e9 totale entre les MCCB n\u00e9cessite des tableaux de coordination minutieux ; les cascades ACB vers MCCB obtiennent de meilleurs r\u00e9sultats car les ACB peuvent r\u00e9ellement retarder (capacit\u00e9 I<sub>cw<\/sub> = I<sub>cu<\/sub> ) tandis que les MCCB g\u00e8rent les d\u00e9fauts en aval<\/li>\n<li>\u2705 <strong>Priorit\u00e9 \u00e0 la s\u00e9curit\u00e9<\/strong>: Les MCCB avanc\u00e9s avec d\u00e9clenchements instantan\u00e9s d\u00e9sactivables (par exemple, Schneider NSX) int\u00e8grent des fonctions de \u201c d\u00e9clenchement \u00e9nerg\u00e9tique \u201d ou de \u201c priorit\u00e9 instantan\u00e9e \u201d - si le courant de d\u00e9faut d\u00e9passe ~ 25 \u00d7 I<sub>n<\/sub>, les m\u00e9canismes \u00e0 gaz forcent le d\u00e9clenchement imm\u00e9diat quels que soient les r\u00e9glages<\/li>\n<\/ul>\n<hr \/>\n<h2>Comprendre les cat\u00e9gories de s\u00e9lectivit\u00e9 de la norme CEI 60947-2<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/Size-and-construction-comparison-between-ACB-with-Icw-rating-and-compact-MCCB-Category-A-breaker.webp\" alt=\"Size and construction comparison between ACB with Icw rating and compact MCCB Category A breaker - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">Comparaison de la taille et de la construction entre un ACB avec indice Icw et un disjoncteur compact MCCB de cat\u00e9gorie A \u2013 VIOX Electric<\/figcaption><\/figure>\n<h3>Cat\u00e9gorie B : ACB avec I d\u00e9clar\u00e9e<sub>cw<\/sub><\/h3>\n<p>Les disjoncteurs de puissance (ACB) sont con\u00e7us pour <strong>Cat\u00e9gorie B<\/strong> les applications o\u00f9 la s\u00e9lectivit\u00e9 est obtenue gr\u00e2ce \u00e0 des temporisations intentionnelles. Selon la norme CEI 60947-2, ces appareils doivent d\u00e9clarer un courant admissible de court-circuit nominal (I<sub>cw<\/sub>) - le courant de d\u00e9faut maximal que le disjoncteur peut supporter en position ferm\u00e9e pendant une dur\u00e9e sp\u00e9cifi\u00e9e (0,05 s, 0,1 s, 0,25 s, 0,5 s ou 1,0 s) sans subir de dommages.<\/p>\n<p><strong>Principales caract\u00e9ristiques des disjoncteurs de cat\u00e9gorie B :<\/strong><\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Param\u00e8tre<\/th>\n<th>Sp\u00e9cification<\/th>\n<th>But<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>I<sub>cw<\/sub> Evaluation<\/strong><\/td>\n<td>Minimum 12 \u00d7 I<sub>n<\/sub> ou 5 kA (cadres \u2264 2500 A)<br \/>\nMinimum 30 kA (cadres &gt; 2500 A)<\/td>\n<td>Permet un retard intentionnel pendant les d\u00e9fauts<\/td>\n<\/tr>\n<tr>\n<td><strong>Contact Design<\/strong><\/td>\n<td>Pression de ressort \u00e9lev\u00e9e<\/td>\n<td>Emp\u00eache la r\u00e9pulsion des contacts pendant la p\u00e9riode de retard<\/td>\n<\/tr>\n<tr>\n<td><strong>Possibilit\u00e9 de diff\u00e9rer le d\u00e9clenchement<\/strong><\/td>\n<td>Le d\u00e9clenchement instantan\u00e9 peut \u00eatre d\u00e9sactiv\u00e9<\/td>\n<td>Permet une coordination purement temporelle<\/td>\n<\/tr>\n<tr>\n<td><strong>Application Typique<\/strong><\/td>\n<td>Arriv\u00e9es principales, d\u00e9parts de distribution<\/td>\n<td>Se coordonne avec les MCCB en aval<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Par exemple, un ACB de 800 A avec I<sub>cw<\/sub> = 85 kA\/1 s peut supporter un courant de d\u00e9faut de 85 kA pendant une dur\u00e9e maximale de 1 seconde pendant que le relais de court d\u00e9lai \u201c attend \u201d que les appareils en aval \u00e9liminent le d\u00e9faut. Cette capacit\u00e9 n\u00e9cessite une construction m\u00e9canique robuste - bras de contact renforc\u00e9s, pression de contact \u00e9lev\u00e9e (emp\u00eachant la r\u00e9pulsion \u00e9lectromagn\u00e9tique) et masse thermique pour absorber l'\u00e9nergie I<sup>2<\/sup>t.<\/p>\n<h3>Cat\u00e9gorie A : MCCB sans I d\u00e9clar\u00e9e<sub>cw<\/sub><\/h3>\n<p>Les disjoncteurs \u00e0 bo\u00eetier moul\u00e9 (MCCB) rel\u00e8vent g\u00e9n\u00e9ralement de <strong>Cat\u00e9gorie A<\/strong>- appareils \u201c non sp\u00e9cifiquement destin\u00e9s \u00e0 la s\u00e9lectivit\u00e9 dans des conditions de court-circuit \u201d selon la norme CEI 60947-2. Ces disjoncteurs ne d\u00e9clarent pas de valeurs I<sub>cw<\/sub> car leur philosophie de conception privil\u00e9gie <strong>une interruption rapide des d\u00e9fauts<\/strong> plut\u00f4t qu'une tenue prolong\u00e9e aux d\u00e9fauts.<\/p>\n<p><strong>Pourquoi les MCCB ne d\u00e9clarent-ils pas I<sub>cw<\/sub>:<\/strong><\/p>\n<ol>\n<li><strong>Conception de limitation de courant<\/strong>: La pression du ressort de contact est intentionnellement faible pour faciliter une r\u00e9pulsion \u00e9lectromagn\u00e9tique rapide lorsque le courant de d\u00e9faut d\u00e9passe ~ 10-14 \u00d7 I<sub>n<\/sub><\/li>\n<li><strong>Mandat de d\u00e9clenchement instantan\u00e9<\/strong>: La plupart des MCCB ne peuvent pas d\u00e9sactiver la protection instantan\u00e9e - tout d\u00e9faut d\u00e9passant le seuil instantan\u00e9 d\u00e9clenche un d\u00e9clenchement imm\u00e9diat<\/li>\n<li><strong>Limites thermiques<\/strong>: La construction moul\u00e9e compacte ne peut pas dissiper l'\u00e9nergie thermique (I<sup>2<\/sup>t) associ\u00e9e \u00e0 une tenue prolong\u00e9e aux courants \u00e9lev\u00e9s<\/li>\n<\/ol>\n<p>Cependant, cela ne <strong>pas<\/strong> signifie pas que les MCCB manquent totalement de capacit\u00e9 de tenue aux courts retards - ils poss\u00e8dent un seuil inh\u00e9rent et non d\u00e9clar\u00e9 en dessous duquel les contacts restent ferm\u00e9s.<\/p>\n<hr \/>\n<h2>La physique de la r\u00e9pulsion des contacts des MCCB<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/MCCB-electromagnetic-contact-repulsion-mechanism-diagram-showing-force-balance-and-current-thresholds.webp\" alt=\"MCCB electromagnetic contact repulsion mechanism diagram showing force balance and current thresholds - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">Sch\u00e9ma du m\u00e9canisme de r\u00e9pulsion \u00e9lectromagn\u00e9tique des contacts des MCCB montrant l'\u00e9quilibre des forces et les seuils de courant \u2013 VIOX Electric<\/figcaption><\/figure>\n<h3>Seuil de r\u00e9pulsion \u00e9lectromagn\u00e9tique<\/h3>\n<p>Lorsque le courant de d\u00e9faut circule dans les chemins de contact parall\u00e8les d'un MCCB, il g\u00e9n\u00e8re des champs magn\u00e9tiques oppos\u00e9s qui cr\u00e9ent <strong>forces de r\u00e9pulsion \u00e9lectrodynamiques<\/strong> (force de Lorentz). Le ressort de contact doit contrer cette force pour maintenir les contacts ferm\u00e9s.<\/p>\n<p><strong>\u00c9quation d'\u00e9quilibre des forces :<\/strong><\/p>\n<p style=\"text-align: center; background-color: #f9f9f9; padding: 10px; border-radius: 4px;\">F<sub>ressort<\/sub> &gt; F<sub>r\u00e9pulsion<\/sub> = k \u00b7 I<sup>2<\/sup><\/p>\n<p>O\u00f9 ?<\/p>\n<ul>\n<li>F<sub>ressort<\/sub> = Force de compression du ressort de contact<\/li>\n<li>F<sub>r\u00e9pulsion<\/sub> = Force de r\u00e9pulsion \u00e9lectromagn\u00e9tique (proportionnelle \u00e0 I<sup>2<\/sup>)<\/li>\n<li>k = Constante g\u00e9om\u00e9trique (espacement des contacts, configuration du conducteur)<\/li>\n<\/ul>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Param\u00e8tre de conception du MCCB<\/th>\n<th>Cat\u00e9gorie A (MCCB)<\/th>\n<th>Cat\u00e9gorie B (ACB)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>Pression du ressort de contact<\/strong><\/td>\n<td>Faible (2-5 N\/mm)<\/td>\n<td>\u00c9lev\u00e9e (10-20 N\/mm)<\/td>\n<\/tr>\n<tr>\n<td><strong>Seuil de r\u00e9pulsion<\/strong><\/td>\n<td>12-14\u00d7 I<sub>n<\/sub><\/td>\n<td>&gt;50\u00d7 I<sub>n<\/sub><\/td>\n<\/tr>\n<tr>\n<td><strong>Vitesse d'ouverture des contacts<\/strong><\/td>\n<td>3-7 ms (ultra-rapide)<\/td>\n<td>20-50 ms (contr\u00f4l\u00e9e)<\/td>\n<\/tr>\n<tr>\n<td><strong>Priorit\u00e9 de conception<\/strong><\/td>\n<td>Limiter l'\u00e9nergie de d\u00e9faut (I<sup>2<\/sup>t)<\/td>\n<td>Tenir compte de la dur\u00e9e du d\u00e9faut<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Consid\u00e9rations sur le d\u00e9marrage du moteur<\/h3>\n<p>Une \u00e9tude de l'Institut de recherche \u00e9lectrique de Shanghai sur 52 \u00e9chantillons de moteurs a r\u00e9v\u00e9l\u00e9 que le d\u00e9marrage direct (DOL) produit des courants d'appel de premier pic de <strong>8-12\u00d7 I<sub>n<\/sub><\/strong> pour la plupart des moteurs, avec des valeurs aberrantes atteignant 13\u00d7 I<sub>n<\/sub>.<\/p>\n<p><strong>Ces donn\u00e9es d\u00e9terminent les contraintes de conception des MCCB :<\/strong><\/p>\n<ul>\n<li><strong>MCCB de distribution<\/strong>: D\u00e9clenchement instantan\u00e9 r\u00e9gl\u00e9 \u00e0 10-12\u00d7 I<sub>n<\/sub> (ne doit pas se d\u00e9clencher lors de l'appel de courant du condensateur ou de la mise sous tension du transformateur)<\/li>\n<li><strong>MCCB \u00e0 calibre moteur<\/strong>: D\u00e9clenchement instantan\u00e9 r\u00e9gl\u00e9 \u00e0 13-14\u00d7 I<sub>n<\/sub> (doit supporter le d\u00e9marrage DOL)<\/li>\n<li><strong>Seuil de r\u00e9pulsion des contacts<\/strong>: Doit d\u00e9passer le r\u00e9glage de d\u00e9clenchement instantan\u00e9 d'une marge de 15 \u00e0 20% pour \u00e9viter une ouverture intempestive des contacts pendant les transitoires de d\u00e9marrage<\/li>\n<\/ul>\n<p><strong>Exemple de calcul pour un MCCB \u00e0 calibre moteur de 100 A :<\/strong><\/p>\n<div style=\"background-color: #f5f5f5; padding: 15px; border-radius: 5px; margin: 15px 0; font-family: monospace;\">R\u00e9glage du d\u00e9clenchement instantan\u00e9 : 13 \u00d7 100 A = 1 300 A<br \/>\nSeuil de r\u00e9pulsion des contacts : 1 300 A \u00d7 1,2 = 1 560 A (objectif de conception)<br \/>\nCapacit\u00e9 \u201cIcw\u201d non d\u00e9clar\u00e9e : ~1 500 A (en dessous du seuil de r\u00e9pulsion)<\/div>\n<p>Ce seuil de 1 500 A repr\u00e9sente la capacit\u00e9 de tenue aux courts-circuits inh\u00e9rente au MCCB, suffisante pour la coordination avec les dispositifs en aval dans la plage de d\u00e9fauts de 1 000 \u00e0 1 500 A, mais bien inf\u00e9rieure aux valeurs I<sub>cw<\/sub> d\u00e9clar\u00e9es des ACB (g\u00e9n\u00e9ralement de 30 \u00e0 85 kA).<\/p>\n<hr \/>\n<h2>Comment fonctionne r\u00e9ellement le d\u00e9lai court du MCCB<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/Technical-infographic-clean-202601280514.webp\" alt=\"MCCB three-zone protection logic diagram showing overload, short-time delay, and instantaneous trip thresholds - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">Sch\u00e9ma logique de protection \u00e0 trois zones du MCCB montrant les seuils de surcharge, de d\u00e9lai court et de d\u00e9clenchement instantan\u00e9 - VIOX Electric<\/figcaption><\/figure>\n<h3>Les trois zones de fonctionnement<\/h3>\n<p>Les MCCB modernes \u00e0 d\u00e9clenchement \u00e9lectronique comportent trois zones de protection, mais leur interaction diff\u00e8re fondamentalement de celle des ACB :<\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Zone de protection<\/th>\n<th>Plage de r\u00e9glage<\/th>\n<th>Comportement r\u00e9el<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>Longue dur\u00e9e (surcharge)<\/strong><\/td>\n<td>0,4-1,0\u00d7 I<sub>n<\/sub>, 3-30s<\/td>\n<td>Protection thermique via le calcul I<sup>2<\/sup>t<\/td>\n<\/tr>\n<tr>\n<td><strong>D\u00e9lai court<\/strong><\/td>\n<td>2-12\u00d7 I<sub>n<\/sub>, 0,1-0,5s<\/td>\n<td><strong>Uniquement actif en dessous du seuil instantan\u00e9<\/strong><\/td>\n<\/tr>\n<tr>\n<td><strong>Instantan\u00e9<\/strong><\/td>\n<td>10-14\u00d7 I<sub>n<\/sub> (fixe ou r\u00e9glable)<\/td>\n<td><strong>Ne peut pas \u00eatre d\u00e9sactiv\u00e9 dans la plupart des MCCB<\/strong><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Sc\u00e9nario 1 : Courant de d\u00e9faut inf\u00e9rieur au seuil instantan\u00e9<\/h3>\n<p><strong>Conditions<\/strong>: Courant de d\u00e9faut = 8\u00d7 I<sub>n<\/sub> (800 A pour un disjoncteur de 100 A)<\/p>\n<ol>\n<li>Le courant d\u00e9passe la zone de longue dur\u00e9e \u2192 Le d\u00e9lai de courte dur\u00e9e s'active<\/li>\n<li>Le d\u00e9clencheur \u00e9lectronique d\u00e9marre le compte \u00e0 rebours (par exemple, 0,4 s)<\/li>\n<li>Si le d\u00e9faut persiste, la bobine de d\u00e9clenchement s'excite apr\u00e8s un d\u00e9lai<\/li>\n<li>Les contacts s'ouvrent via un m\u00e9canisme \u00e0 \u00e9nergie emmagasin\u00e9e (temps d'ouverture d'environ 20 \u00e0 30 ms)<\/li>\n<\/ol>\n<p><strong>R\u00e9sultat<\/strong>: Coordination v\u00e9ritablement temporis\u00e9e avec les dispositifs en aval<\/p>\n<h3>Sc\u00e9nario 2 : Courant de d\u00e9faut sup\u00e9rieur au seuil instantan\u00e9<\/h3>\n<p><strong>Conditions<\/strong>: Courant de d\u00e9faut = 15 \u00d7 I<sub>n<\/sub> (1 500 A pour un disjoncteur de 100 A)<\/p>\n<ol>\n<li>Le courant d\u00e9passe le seuil instantan\u00e9 \u2192 Le d\u00e9clenchement magn\u00e9tique s'active imm\u00e9diatement<\/li>\n<li>Le r\u00e9glage du d\u00e9lai de courte dur\u00e9e est <strong>contourn\u00e9<\/strong><\/li>\n<li>La bobine de d\u00e9clenchement s'excite en 5 \u00e0 10 ms<\/li>\n<li>Les contacts s'ouvrent, mais le courant de d\u00e9faut peut d\u00e9j\u00e0 avoir provoqu\u00e9 une r\u00e9pulsion \u00e9lectromagn\u00e9tique<\/li>\n<\/ol>\n<p><strong>R\u00e9sultat<\/strong>: Pas de d\u00e9lai intentionnel : le MCCB se d\u00e9clenche aussi vite que possible<\/p>\n<h3>Sc\u00e9nario 3 : Courant de d\u00e9faut d\u00e9passant de loin le seuil de r\u00e9pulsion<\/h3>\n<p><strong>Conditions<\/strong>: Courant de d\u00e9faut = 50 \u00d7 I<sub>n<\/sub> (5 000 A pour un disjoncteur de 100 A, approchant I<sub>cu<\/sub>)<\/p>\n<ol>\n<li>La force de r\u00e9pulsion \u00e9lectromagn\u00e9tique d\u00e9passe la pression du ressort<\/li>\n<li>Les contacts s'\u00e9cartent en 3 \u00e0 7 ms (plus vite que le m\u00e9canisme de d\u00e9clenchement)<\/li>\n<li>La tension d'arc augmente rapidement, limitant le courant de cr\u00eate (action de limitation de courant)<\/li>\n<li>L'\u00e9nergie de l'arc peut d\u00e9clencher le m\u00e9canisme de d\u00e9clenchement, ou le disjoncteur repose uniquement sur l'extinction de l'arc<\/li>\n<\/ol>\n<p><strong>R\u00e9sultat<\/strong>: Limitation de courant ultra-rapide : pas de coordination, mais protection de l'\u00e9quipement via la r\u00e9duction de I<sup>2<\/sup>t<\/p>\n<hr \/>\n<h2>Cas particulier : MCCB avec d\u00e9clenchement instantan\u00e9 d\u00e9sactivable<\/h2>\n<h3>M\u00e9canisme de \u201cd\u00e9clenchement \u00e9nerg\u00e9tique\u201d Schneider NSX<\/h3>\n<p>Certains MCCB haut de gamme (par exemple, Schneider Electric NSX avec d\u00e9clencheurs Micrologic) permettent de d\u00e9sactiver la protection instantan\u00e9e pour une s\u00e9lectivit\u00e9 am\u00e9lior\u00e9e. Cependant, ces dispositifs int\u00e8grent une <strong>priorit\u00e9 de s\u00e9curit\u00e9 obligatoire<\/strong> appel\u00e9e \u201cd\u00e9clenchement \u00e9nerg\u00e9tique\u201d ou \u201cpriorit\u00e9 instantan\u00e9e\u201d.\u201d<\/p>\n<p><strong>Comment \u00e7a marche :<\/strong><\/p>\n<ol>\n<li>L'utilisateur d\u00e9sactive le d\u00e9clenchement instantan\u00e9, active le d\u00e9lai de courte dur\u00e9e (par exemple, 10 \u00d7 I<sub>n<\/sub>, 0,4 s)<\/li>\n<li>Le courant de d\u00e9faut atteint 30 \u00d7 I<sub>n<\/sub> (3 000 A pour un disjoncteur de 100 A)<\/li>\n<li>Les contacts se repoussent, un arc se forme<\/li>\n<li>L'\u00e9nergie de l'arc ionise le mat\u00e9riau g\u00e9n\u00e9rateur de gaz dans la chambre d'arc<\/li>\n<li>L'augmentation de la pression actionne le m\u00e9canisme de d\u00e9clenchement pneumatique en 10 \u00e0 15 ms<\/li>\n<li>Le disjoncteur se d\u00e9clenche <strong>quels que soient les r\u00e9glages du d\u00e9clencheur \u00e9lectronique<\/strong><\/li>\n<\/ol>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Niveau de courant de d\u00e9faut<\/th>\n<th>R\u00e9ponse NSX<\/th>\n<th>R\u00e9ponse MCCB standard<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>8 \u00d7 I<sub>n<\/sub><\/strong><\/td>\n<td>Le d\u00e9lai de courte dur\u00e9e fonctionne normalement<\/td>\n<td>Fonctions de d\u00e9lai de courte dur\u00e9e<\/td>\n<\/tr>\n<tr>\n<td><strong>15 \u00d7 I<sub>n<\/sub><\/strong><\/td>\n<td>Fonctions de d\u00e9lai de courte dur\u00e9e (inst. d\u00e9sactiv\u00e9)<\/td>\n<td>D\u00e9clenchement instantan\u00e9 (impossible \u00e0 d\u00e9sactiver)<\/td>\n<\/tr>\n<tr>\n<td><strong>&gt; 25 \u00d7 I<sub>n<\/sub><\/strong><\/td>\n<td>Le d\u00e9clenchement \u00e9nerg\u00e9tique remplace le d\u00e9lai<\/td>\n<td>R\u00e9pulsion des contacts + d\u00e9clenchement instantan\u00e9<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Cette conception emp\u00eache une d\u00e9faillance catastrophique lorsque les utilisateurs configurent mal les param\u00e8tres de protection : le MCCB s'autoprotegera toujours en cas de d\u00e9faut extr\u00eame, m\u00eame si cela compromet la s\u00e9lectivit\u00e9.<\/p>\n<hr \/>\n<h2>Strat\u00e9gies de coordination pratiques<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/Time-current-coordination-diagram-showing-ACB-and-MCCB-selectivity-zones-with-fault-scenario-analysis.webp\" alt=\"Time-current coordination diagram showing ACB and MCCB selectivity zones with fault scenario analysis - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">Diagramme de coordination temps-courant montrant les zones de s\u00e9lectivit\u00e9 ACB et MCCB avec analyse de sc\u00e9nario de d\u00e9faut \u2013 VIOX Electric<\/figcaption><\/figure>\n<h3>Strat\u00e9gie 1 : Cascade ACB-vers-MCCB (recommand\u00e9e)<\/h3>\n<p><strong>Configuration :<\/strong><\/p>\n<ul>\n<li><strong>En amont<\/strong>: ACB 1600 A, I<sub>cw<\/sub> = 65 kA\/0,5 s, d\u00e9lai de courte dur\u00e9e = 0,4 s<\/li>\n<li><strong>En aval<\/strong>: MCCB 400 A, I<sub>cu<\/sub> = 50 kA, instantan\u00e9 = 5 000 A (12,5 \u00d7 I<sub>n<\/sub>)<\/li>\n<\/ul>\n<p><strong>Analyse de la coordination :<\/strong><\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Emplacement du d\u00e9faut<\/th>\n<th>Courant de d\u00e9faut<\/th>\n<th>Action ACB en amont<\/th>\n<th>Action MCCB en aval<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>D\u00e9part en aval<\/strong><\/td>\n<td>8 kA<\/td>\n<td>Attend 0,4 s (dans I<sub>cw<\/sub>)<\/td>\n<td>D\u00e9clenche instantan\u00e9ment (&gt;12,5\u00d7 I<sub>n<\/sub>)<\/td>\n<\/tr>\n<tr>\n<td><strong>D\u00e9part en aval<\/strong><\/td>\n<td>45 kA<\/td>\n<td>Attend 0,4 s (dans I<sub>cw<\/sub>)<\/td>\n<td>D\u00e9clenche instantan\u00e9ment (limitation de courant)<\/td>\n<\/tr>\n<tr>\n<td><strong>Jeu de barres principal<\/strong><\/td>\n<td>60 kA<\/td>\n<td>D\u00e9clenche apr\u00e8s 0,4 s<\/td>\n<td>Non affect\u00e9<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><strong>R\u00e9sultat<\/strong>: S\u00e9lectivit\u00e9 totale jusqu'\u00e0 50 kA (MCCB I<sub>cu<\/sub> limite)<\/p>\n<h3>Strat\u00e9gie 2\u00a0: Coordination MCCB \u00e0 MCCB (limit\u00e9e)<\/h3>\n<p><strong>Configuration :<\/strong><\/p>\n<ul>\n<li><strong>En amont<\/strong>: MCCB 400\u00a0A, instantan\u00e9 = 5\u00a0000\u00a0A (12,5\u00d7 I<sub>n<\/sub>)<\/li>\n<li><strong>En aval<\/strong>: MCCB 100\u00a0A, instantan\u00e9 = 1\u00a0300\u00a0A (13\u00d7 I<sub>n<\/sub>)<\/li>\n<\/ul>\n<p><strong>Analyse de la coordination :<\/strong><\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Courant de d\u00e9faut<\/th>\n<th>MCCB en amont<\/th>\n<th>MCCB en aval<\/th>\n<th>S\u00e9lectivit\u00e9\u00a0?<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>1 500 A<\/strong><\/td>\n<td>Temporisation courte (0,3\u00a0s)<\/td>\n<td>Voyage instantan\u00e9<\/td>\n<td>\u2705 Oui<\/td>\n<\/tr>\n<tr>\n<td><strong>4\u00a0000\u00a0A<\/strong><\/td>\n<td>Temporisation courte (0,3\u00a0s)<\/td>\n<td>Voyage instantan\u00e9<\/td>\n<td>\u2705 Oui<\/td>\n<\/tr>\n<tr>\n<td><strong>6\u00a0000\u00a0A<\/strong><\/td>\n<td><strong>Voyage instantan\u00e9<\/strong><\/td>\n<td>Voyage instantan\u00e9<\/td>\n<td>\u274c Non (les deux d\u00e9clenchent)<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><strong>Limite de s\u00e9lectivit\u00e9<\/strong>: ~4\u00a0500\u00a0A (90% du r\u00e9glage instantan\u00e9 en amont)<\/p>\n<p><strong>Am\u00e9lioration<\/strong>: Utilisez les tableaux de coordination du fabricant pour v\u00e9rifier l'\u00e9nergie traversante r\u00e9elle\u00a0: les MCCB \u00e0 limitation de courant peuvent toujours atteindre la s\u00e9lectivit\u00e9 \u00e0 des niveaux de d\u00e9faut plus \u00e9lev\u00e9s gr\u00e2ce \u00e0 la discrimination I<sup>2<\/sup>t.<\/p>\n<hr \/>\n<h2>Tableau comparatif\u00a0: Caract\u00e9ristiques de court retard ACB vs. MCCB<\/h2>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Fonctionnalit\u00e9<\/th>\n<th>ACB (Cat\u00e9gorie\u00a0B)<\/th>\n<th>MCCB (Cat\u00e9gorie\u00a0A)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>I<sub>cw<\/sub> D\u00e9claration<\/strong><\/td>\n<td>\u2705 Oui (30-85\u00a0kA, 0,05-1,0\u00a0s)<\/td>\n<td>\u274c Non (non d\u00e9clar\u00e9)<\/td>\n<\/tr>\n<tr>\n<td><strong>Tenue inh\u00e9rente<\/strong><\/td>\n<td>Tr\u00e8s \u00e9lev\u00e9e (&gt;50\u00d7 I<sub>n<\/sub>)<\/td>\n<td>Limit\u00e9e (12-14\u00d7 I<sub>n<\/sub>)<\/td>\n<\/tr>\n<tr>\n<td><strong>Pression du ressort de contact<\/strong><\/td>\n<td>\u00c9lev\u00e9e (emp\u00eache la r\u00e9pulsion)<\/td>\n<td>Faible (permet la limitation de courant)<\/td>\n<\/tr>\n<tr>\n<td><strong>D\u00e9clenchement instantan\u00e9<\/strong><\/td>\n<td>Peut \u00eatre d\u00e9sactiv\u00e9e<\/td>\n<td>G\u00e9n\u00e9ralement fixe (ne peut pas \u00eatre d\u00e9sactiv\u00e9e)<\/td>\n<\/tr>\n<tr>\n<td><strong>Plage de temporisation courte<\/strong><\/td>\n<td>0,05-1,0\u00a0s (r\u00e9glable)<\/td>\n<td>0,1-0,5\u00a0s (uniquement en dessous du seuil inst.)<\/td>\n<\/tr>\n<tr>\n<td><strong>M\u00e9thode de coordination<\/strong><\/td>\n<td>Bas\u00e9e sur le temps (retard r\u00e9el)<\/td>\n<td>Bas\u00e9e sur le courant (limitation + retard)<\/td>\n<\/tr>\n<tr>\n<td><strong>Application Typique<\/strong><\/td>\n<td>Arriv\u00e9e principale (1\u00a0000-6\u00a0300\u00a0A)<\/td>\n<td>Protection de d\u00e9part (16-1\u00a0600\u00a0A)<\/td>\n<\/tr>\n<tr>\n<td><strong>S\u00e9lectivit\u00e9 avec l'aval<\/strong><\/td>\n<td>Totale (jusqu'\u00e0 I<sub>cw<\/sub>)<\/td>\n<td>Partielle (jusqu'au seuil inst.)<\/td>\n<\/tr>\n<tr>\n<td><strong>M\u00e9canisme d'autoprotection<\/strong><\/td>\n<td>Masse thermique + r\u00e9sistance m\u00e9canique<\/td>\n<td>R\u00e9pulsion des contacts + limitation d'arc<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<hr \/>\n<h2>Pourquoi c'est important pour la conception du syst\u00e8me<\/h2>\n<h3>Id\u00e9e fausse\u00a01\u00a0: \u201c\u00a0Court retard MCCB = Court retard ACB\u00a0\u201d<\/h3>\n<p><strong>R\u00e9alit\u00e9<\/strong>: Le court retard MCCB ne fonctionne que dans une fen\u00eatre de courant \u00e9troite (entre les seuils de longue dur\u00e9e et instantan\u00e9s). Pour les d\u00e9fauts d\u00e9passant les r\u00e9glages instantan\u00e9s, les MCCB d\u00e9clenchent imm\u00e9diatement\u00a0: aucun retard ne se produit.<\/p>\n<p><strong>Impact sur la conception<\/strong>: Lors de la sp\u00e9cification de la protection MCCB, v\u00e9rifiez toujours\u00a0:<\/p>\n<ol>\n<li>Les r\u00e9glages instantan\u00e9s du dispositif en aval<\/li>\n<li>Le courant de d\u00e9faut maximal au point de coordination<\/li>\n<li>Si le courant de d\u00e9faut d\u00e9passera le seuil instantan\u00e9 du MCCB en amont<\/li>\n<\/ol>\n<h3>Id\u00e9e fausse\u00a02\u00a0: \u201c\u00a0Pas de I<sub>cw<\/sub> nominal = Pas de capacit\u00e9 de court-circuit\u00a0\u201d<\/h3>\n<p><strong>R\u00e9alit\u00e9<\/strong>: Les MCCB poss\u00e8dent une tenue inh\u00e9rente aux courts-circuits jusqu'\u00e0 leur seuil de r\u00e9pulsion des contacts (~12-14\u00d7 I<sub>n<\/sub>). Cette capacit\u00e9 permet une coordination limit\u00e9e avec les dispositifs en aval, mais pas dans la m\u00eame mesure que les ACB.<\/p>\n<p><strong>Impact sur la conception<\/strong>: La coordination MCCB \u00e0 MCCB est possible, mais n\u00e9cessite\u00a0:<\/p>\n<ul>\n<li>Une s\u00e9paration minutieuse des r\u00e9glages instantan\u00e9s (rapport minimum de 1,5:1)<\/li>\n<li>Des tableaux de s\u00e9lectivit\u00e9 fournis par le fabricant<\/li>\n<li>Examen des effets de limitation de courant sur l'\u00e9nergie traversante<\/li>\n<\/ul>\n<h3>Id\u00e9e fausse n\u00b0 3 : \u201c D\u00e9sactiver le d\u00e9clenchement instantan\u00e9 transforme un MCCB en ACB \u201d<\/h3>\n<p><strong>R\u00e9alit\u00e9<\/strong>: M\u00eame les MCCB avec d\u00e9clenchements instantan\u00e9s d\u00e9sactivables (par exemple, NSX) int\u00e8grent des m\u00e9canismes de priorit\u00e9 bas\u00e9s sur l'\u00e9nergie qui forcent le d\u00e9clenchement \u00e0 des niveaux de d\u00e9faut extr\u00eames (&gt; 25 \u00d7 I<sub>n<\/sub>). Ils ne peuvent pas \u201c attendre \u201d des courants de d\u00e9faut \u00e9lev\u00e9s comme les ACB.<\/p>\n<p><strong>Impact sur la conception<\/strong>: Lors de l'utilisation de MCCB avec instantan\u00e9 r\u00e9glable :<\/p>\n<ul>\n<li>V\u00e9rifiez le seuil de d\u00e9clenchement \u00e9nerg\u00e9tique aupr\u00e8s du fabricant<\/li>\n<li>Ne pr\u00e9sumez pas un comportement de type ACB aux courants de d\u00e9faut approchant I<sub>cu<\/sub><\/li>\n<li>Tenez compte des implications \u00e9nerg\u00e9tiques des arcs \u00e9lectriques d'un d\u00e9clenchement retard\u00e9<\/li>\n<\/ul>\n<hr \/>\n<h2>Liens internes et ressources connexes<\/h2>\n<p>Pour une compr\u00e9hension plus approfondie des concepts de protection connexes, explorez ces guides techniques VIOX :<\/p>\n<ul>\n<li><a href=\"https:\/\/test.viox.com\/fr\/electrical-derating-temperature-altitude-grouping-factors\/\"><strong>D\u00e9classement \u00e9lectrique : Temp\u00e9rature, altitude et facteurs de groupement<\/strong><\/a> \u2013 D\u00e9couvrez comment les facteurs environnementaux affectent les valeurs nominales de courant et la coordination des disjoncteurs<\/li>\n<li><a href=\"https:\/\/test.viox.com\/fr\/ats-circuit-breaker-coordination-guide-icw-selectivity\/\"><strong>Guide de coordination ATS et disjoncteur : I<sub>cw<\/sub> et s\u00e9lectivit\u00e9 expliqu\u00e9es<\/strong><\/a> \u2013 Analyse d\u00e9taill\u00e9e de la coordination de cat\u00e9gorie A par rapport \u00e0 la cat\u00e9gorie B dans les applications de commutateurs de transfert automatique<\/li>\n<li><a href=\"https:\/\/test.viox.com\/fr\/current-limiting-circuit-breaker-guide\/\"><strong>Guide du Disjoncteur Limiteur de Courant : Protection et Sp\u00e9cifications<\/strong><\/a> \u2013 Plong\u00e9e en profondeur dans la physique de la r\u00e9pulsion \u00e9lectromagn\u00e9tique et la limitation I<sup>2<\/sup>t<\/li>\n<li><a href=\"https:\/\/test.viox.com\/fr\/types-of-circuit-breakers\/\"><strong>Types de disjoncteurs : Guide complet de classification<\/strong><\/a> \u2013 Aper\u00e7u complet des diff\u00e9rences et des applications entre ACB, MCCB et MCB<\/li>\n<li><a href=\"https:\/\/test.viox.com\/fr\/commercial-ev-charging-protection-guide-acb-mccb-rcbo\/\"><strong>Guide de protection de la recharge commerciale de v\u00e9hicules \u00e9lectriques : ACB, MCCB et RCBO de type B<\/strong><\/a> \u2013 Exemple de coordination r\u00e9el avec calculs de charge<\/li>\n<\/ul>\n<hr \/>\n<h2>FAQ : Protection court retard des MCCB<\/h2>\n<h3>Q1 : Puis-je utiliser un MCCB comme arriv\u00e9e principale au lieu d'un ACB ?<\/h3>\n<p><strong>Un<\/strong>: Possible, mais non recommand\u00e9 pour les syst\u00e8mes n\u00e9cessitant une s\u00e9lectivit\u00e9 totale. Les MCCB n'ont pas de valeurs nominales I<sub>cw<\/sub> d\u00e9clar\u00e9es, ils ne peuvent donc pas retarder de mani\u00e8re fiable le d\u00e9clenchement pour la coordination en aval \u00e0 des courants de d\u00e9faut \u00e9lev\u00e9s (&gt; 10 \u00d7 I<sub>n<\/sub>). Utilisez des ACB pour les arriv\u00e9es principales dans les installations industrielles o\u00f9 la s\u00e9lectivit\u00e9 est essentielle, ou v\u00e9rifiez les limites de coordination avec les tableaux du fabricant pour les applications commerciales.<\/p>\n<h3>Q2 : Que se passe-t-il si je r\u00e8gle le d\u00e9lai court retard du MCCB sur 0,5 s, mais que le courant de d\u00e9faut est de 20 \u00d7 I<sub>n<\/sub>?<\/h3>\n<p><strong>Un<\/strong>: Le disjoncteur se d\u00e9clenchera <strong>imm\u00e9diatement<\/strong> via un d\u00e9clenchement magn\u00e9tique, ignorant le r\u00e9glage de d\u00e9lai de 0,5 s. Les d\u00e9lais court retard des MCCB ne fonctionnent que lorsque le courant de d\u00e9faut reste entre la prise en charge court retard (par exemple, 2 \u00e0 10 \u00d7 I<sub>n<\/sub>) et le seuil instantan\u00e9 (par exemple, 12 \u00d7 I<sub>n<\/sub>). Au-dessus de l'instantan\u00e9, l'\u00e9l\u00e9ment magn\u00e9tique remplace les r\u00e9glages \u00e9lectroniques.<\/p>\n<h3>Q3 : Tous les MCCB utilisent-ils la technologie de limitation de courant ?<\/h3>\n<p><strong>Un<\/strong>: Non. Les MCCB thermomagn\u00e9tiques (d\u00e9clenchement fixe, sans r\u00e9glage) utilisent g\u00e9n\u00e9ralement des \u00e9l\u00e9ments de surcharge bim\u00e9talliques plus lents et peuvent ne pas atteindre une v\u00e9ritable limitation de courant. Les MCCB \u00e0 d\u00e9clenchement \u00e9lectronique avec des contacts \u00e0 action rapide et des chambres d'extinction d'arc optimis\u00e9es sont plus susceptibles de limiter le courant (v\u00e9rifiez avec les courbes de courant traversant du fabricant indiquant les valeurs I<sub>p<\/sub> et I<sup>2<\/sup>t inf\u00e9rieures aux niveaux de d\u00e9faut prospectifs).<\/p>\n<h3>Q4 : Comment v\u00e9rifier la s\u00e9lectivit\u00e9 entre deux MCCB ?<\/h3>\n<p><strong>Un<\/strong>: Utilisez les tableaux de coordination du fabricant (pas seulement les courbes temps-courant). Les tableaux tiennent compte de :<\/p>\n<ul>\n<li>L'\u00e9nergie traversante (I<sup>2<\/sup>t) du disjoncteur en aval<\/li>\n<li>Seuil d'\u00e9nergie de non-d\u00e9clenchement du disjoncteur en amont<\/li>\n<li>Effets de limitation de courant \u00e0 diff\u00e9rents niveaux de d\u00e9faut<br \/>\nExemple : Schneider Electric fournit des tableaux de s\u00e9lectivit\u00e9 d\u00e9taill\u00e9s dans ses guides de coordination indiquant les limites de s\u00e9lectivit\u00e9 maximales (par exemple, \u201c S\u00e9lectif jusqu'\u00e0 15 kA \u201d entre des mod\u00e8les de MCCB sp\u00e9cifiques).<\/li>\n<\/ul>\n<h3>Q5 : Pourquoi les MCCB \u00e0 moteur ont-ils des r\u00e9glages instantan\u00e9s plus \u00e9lev\u00e9s (13-14 \u00d7 I<sub>n<\/sub>)?<\/h3>\n<p><strong>Un<\/strong>: Pour \u00e9viter les d\u00e9clenchements intempestifs lors du d\u00e9marrage direct en ligne (DOL) du moteur. La recherche montre que le courant d'appel du moteur peut atteindre 12 \u00e0 13 \u00d7 I<sub>n<\/sub> pour le premier pic. Les MCCB \u00e0 moteur ont \u00e9galement des seuils de r\u00e9pulsion de contact plus \u00e9lev\u00e9s (&gt; 14 \u00d7 I<sub>n<\/sub>) pour garantir que les contacts ne s'ouvrent pas pendant les transitoires de d\u00e9marrage, ce qui entra\u00eenerait une usure inutile et un soudage potentiel lors de la refermeture.<\/p>\n<hr \/>\n<h2>Conclusion<\/h2>\n<p>Le paradoxe apparent des MCCB offrant une protection court retard sans valeurs I<sub>cw<\/sub> nominales d\u00e9coule d'une diff\u00e9rence fondamentale dans la philosophie de protection : <strong>Les ACB r\u00e9sistent aux d\u00e9fauts gr\u00e2ce \u00e0 la r\u00e9sistance m\u00e9canique et \u00e0 la masse thermique, tandis que les MCCB limitent les d\u00e9fauts gr\u00e2ce \u00e0 la physique \u00e9lectromagn\u00e9tique et \u00e0 l'interruption rapide de l'arc.<\/strong><\/p>\n<p>Comprendre cette distinction est essentiel pour les ing\u00e9nieurs \u00e9lectriciens qui con\u00e7oivent des sch\u00e9mas de coordination. Les MCCB peuvent r\u00e9aliser une coordination s\u00e9lective avec les dispositifs en aval dans leur capacit\u00e9 de tenue court retard inh\u00e9rente (g\u00e9n\u00e9ralement 12 \u00e0 14 \u00d7 I<sub>n<\/sub>), mais ils ne peuvent pas reproduire le comportement de l'ACB \u00e0 des courants de d\u00e9faut \u00e9lev\u00e9s approchant leur pouvoir de coupure. Pour les applications n\u00e9cessitant une s\u00e9lectivit\u00e9 totale sur toute la plage de courant de d\u00e9faut, les arriv\u00e9es principales ACB se coordonnant avec les d\u00e9parts MCCB restent la r\u00e9f\u00e9rence, tirant parti des capacit\u00e9s de temporisation de cat\u00e9gorie B en amont tout en exploitant les avantages de limitation de courant de cat\u00e9gorie A en aval.<\/p>\n<p><strong>Principe de conception cl\u00e9<\/strong>: Faites correspondre la cat\u00e9gorie de disjoncteur \u00e0 l'application : utilisez des ACB l\u00e0 o\u00f9 vous devez \u201c attendre \u201d les d\u00e9fauts, utilisez des MCCB l\u00e0 o\u00f9 vous devez \u201c \u00e9liminer les d\u00e9fauts rapidement \u201d.\u201d<\/p>\n<hr \/>\n<p><strong>\u00c0 propos de VIOX Electric<\/strong>: VIOX Electric est un fabricant B2B leader d'\u00e9quipements \u00e9lectriques, sp\u00e9cialis\u00e9 dans les disjoncteurs \u00e0 bo\u00eetier moul\u00e9 (MCCB), les disjoncteurs \u00e0 air (ACB) et les solutions de protection compl\u00e8tes pour les applications industrielles et commerciales. Notre \u00e9quipe d'ing\u00e9nieurs fournit un support technique pour les \u00e9tudes de coordination complexes et l'optimisation de la conception du syst\u00e8me. <a href=\"https:\/\/test.viox.com\/fr\/\">Contactez nous<\/a> pour des conseils sp\u00e9cifiques \u00e0 l'application.<\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>MCCB electronic trip unit in industrial panel showing 400A rating and current display &#8211; VIOX Electric Direct Answer Molded Case Circuit Breakers (MCCBs) can provide short-time delay protection without a rated short-time withstand current (Icw) because they belong to IEC 60947-2 Category A, where selectivity is achieved through current-limiting technology rather than intentional time delays. [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":21475,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"inline_featured_image":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"footnotes":""},"categories":[1],"tags":[],"class_list":["post-21474","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"_links":{"self":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/posts\/21474","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/comments?post=21474"}],"version-history":[{"count":1,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/posts\/21474\/revisions"}],"predecessor-version":[{"id":21476,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/posts\/21474\/revisions\/21476"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/media\/21475"}],"wp:attachment":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/media?parent=21474"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/categories?post=21474"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/tags?post=21474"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}