{"id":18696,"date":"2025-07-20T01:12:14","date_gmt":"2025-07-19T17:12:14","guid":{"rendered":"https:\/\/viox.com\/?p=18696"},"modified":"2025-07-20T01:12:16","modified_gmt":"2025-07-19T17:12:16","slug":"uc-up-mean-on-spd","status":"publish","type":"post","link":"https:\/\/test.viox.com\/fr\/uc-up-mean-on-spd\/","title":{"rendered":"Uc UP Mean on SPD\u00a0: Guide complet des param\u00e8tres de tension des dispositifs de protection contre les surtensions"},"content":{"rendered":"<div class=\"product-intro\">\n<p><strong>Uc et Up sont deux param\u00e8tres de tension critiques qui d\u00e9terminent l&#039;efficacit\u00e9 d&#039;un <a href=\"https:\/\/test.viox.com\/fr\/spd\/\">Dispositif de protection contre les surtensions (SPD)<\/a> prot\u00e9gera votre \u00e9quipement \u00e9lectrique.<\/strong> Uc repr\u00e9sente la tension maximale de fonctionnement continu, tandis que Up indique le niveau de protection contre les surtensions lors de l&#039;activation. Une bonne compr\u00e9hension de ces param\u00e8tres garantit une protection optimale contre les surtensions et pr\u00e9vient les dommages mat\u00e9riels co\u00fbteux.<\/p>\n<h2>Que signifient Uc et Up sur SPD\u00a0? D\u00e9finitions essentielles<\/h2>\n<p><img fetchpriority=\"high\" decoding=\"async\" class=\"alignnone size-full wp-image-5502\" src=\"https:\/\/test.viox.com\/wp-content\/uploads\/2024\/09\/VIOX-VSP1-C40PV_3S-1000VD4-Pluggable-Multi-Pole-SPD01.webp\" alt=\"VIOX VSP1-C40PV\/3(S) 1000V(D4) Pluggable Multi-Pole SPD\" width=\"800\" height=\"800\" srcset=\"https:\/\/test.viox.com\/wp-content\/uploads\/2024\/09\/VIOX-VSP1-C40PV_3S-1000VD4-Pluggable-Multi-Pole-SPD01.webp 800w, https:\/\/test.viox.com\/wp-content\/uploads\/2024\/09\/VIOX-VSP1-C40PV_3S-1000VD4-Pluggable-Multi-Pole-SPD01-300x300.webp 300w, https:\/\/test.viox.com\/wp-content\/uploads\/2024\/09\/VIOX-VSP1-C40PV_3S-1000VD4-Pluggable-Multi-Pole-SPD01-150x150.webp 150w, https:\/\/test.viox.com\/wp-content\/uploads\/2024\/09\/VIOX-VSP1-C40PV_3S-1000VD4-Pluggable-Multi-Pole-SPD01-768x768.webp 768w, https:\/\/test.viox.com\/wp-content\/uploads\/2024\/09\/VIOX-VSP1-C40PV_3S-1000VD4-Pluggable-Multi-Pole-SPD01-600x600.webp 600w, https:\/\/test.viox.com\/wp-content\/uploads\/2024\/09\/VIOX-VSP1-C40PV_3S-1000VD4-Pluggable-Multi-Pole-SPD01-100x100.webp 100w\" sizes=\"(max-width: 800px) 100vw, 800px\" \/><\/p>\n<h3>Uc : Tension maximale de fonctionnement continu<\/h3>\n<p>La tension maximale de fonctionnement continu (Uc) est la tension alternative ou continue maximale pouvant \u00eatre appliqu\u00e9e en continu au parafoudre sans provoquer d&#039;activation ni de d\u00e9gradation. Ce param\u00e8tre d\u00e9termine la p\u00e9riode pendant laquelle le parafoudre reste inactif en fonctionnement normal.<\/p>\n<p><strong>Caract\u00e9ristiques principales de l&#039;UC :<\/strong><\/p>\n<ul>\n<li>Repr\u00e9sente la valeur efficace maximale de la tension alternative qui peut \u00eatre appliqu\u00e9e en continu au mode de protection SPD<\/li>\n<li>Doit d\u00e9passer la tension nominale du syst\u00e8me pour assurer un bon fonctionnement<\/li>\n<li>Si la valeur choisie est trop \u00e9lev\u00e9e, le SPD peut ne pas s&#039;activer pendant les \u00e9v\u00e9nements de surtension<\/li>\n<li>Le d\u00e9passement de Uc entra\u00eenera une surchauffe du parasurtenseur, un vieillissement acc\u00e9l\u00e9r\u00e9 et potentiellement des dommages.<\/li>\n<\/ul>\n<h3>Haut : Niveau de protection de tension<\/h3>\n<p>Up (Voltage Protection Level) est la tension maximale aux bornes du SPD lorsqu&#039;il est actif, atteinte lorsque le courant traversant le SPD est \u00e9gal au courant de d\u00e9charge nominal (In).<\/p>\n<p><strong>Caract\u00e9ristiques principales de Up :<\/strong><\/p>\n<ul>\n<li>Pour les parasurtenseurs de type interrupteur de tension, Up est la tension de d\u00e9charge maximale<\/li>\n<li>Pour les parasurtenseurs de type pince, Up repr\u00e9sente la tension de cr\u00eate apparaissant aux bornes pendant la d\u00e9charge<\/li>\n<li>Doit \u00eatre inf\u00e9rieur \u00e0 la capacit\u00e9 de r\u00e9sistance aux surtensions de l&#039;\u00e9quipement prot\u00e9g\u00e9<\/li>\n<li>Des valeurs Up inf\u00e9rieures offrent une meilleure protection pour les \u00e9quipements sensibles<\/li>\n<\/ul>\n<p><img decoding=\"async\" class=\"alignnone  wp-image-18715\" src=\"https:\/\/test.viox.com\/wp-content\/uploads\/2025\/07\/current-characteristic-of-a-SPD.webp\" alt=\"current characteristic of a SPD\" width=\"513\" height=\"402\" srcset=\"https:\/\/test.viox.com\/wp-content\/uploads\/2025\/07\/current-characteristic-of-a-SPD.webp 352w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/07\/current-characteristic-of-a-SPD-300x235.webp 300w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/07\/current-characteristic-of-a-SPD-15x12.webp 15w\" sizes=\"(max-width: 513px) 100vw, 513px\" \/><\/p>\n<h2>Tableau de comparaison SPD Uc et Up<\/h2>\n<table>\n<thead>\n<tr>\n<th>Param\u00e8tre<\/th>\n<th>Uc (tension maximale de fonctionnement continu)<\/th>\n<th>Up (niveau de protection de tension)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>D\u00e9finition<\/strong><\/td>\n<td>Tension maximale pour un fonctionnement continu<\/td>\n<td>Tension maximale pendant la protection contre les surtensions<\/td>\n<\/tr>\n<tr>\n<td><strong>Fonction<\/strong><\/td>\n<td>D\u00e9termine le seuil d&#039;activation du SPD<\/td>\n<td>Limite la surtension des \u00e9quipements<\/td>\n<\/tr>\n<tr>\n<td><strong>Crit\u00e8res de s\u00e9lection<\/strong><\/td>\n<td>Doit d\u00e9passer la tension nominale du syst\u00e8me<\/td>\n<td>Doit \u00eatre inf\u00e9rieure \u00e0 la tension de tenue de l&#039;\u00e9quipement<\/td>\n<\/tr>\n<tr>\n<td><strong>Valeurs typiques (syst\u00e8me 230 V)<\/strong><\/td>\n<td>275 V, 320 V, 385 V<\/td>\n<td>1,5 kV, 2,5 kV, 4 kV<\/td>\n<\/tr>\n<tr>\n<td><strong>Impact sur la s\u00e9curit\u00e9<\/strong><\/td>\n<td>Emp\u00eache l&#039;activation pr\u00e9matur\u00e9e<\/td>\n<td>Emp\u00eache les dommages \u00e0 l&#039;\u00e9quipement<\/td>\n<\/tr>\n<tr>\n<td><strong>Standard Reference<\/strong><\/td>\n<td>IEC 61643-11<\/td>\n<td>IEC 61643-11<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><img decoding=\"async\" class=\"alignnone size-full wp-image-17672\" src=\"https:\/\/test.viox.com\/wp-content\/uploads\/2025\/06\/VIOX-SPD.webp\" alt=\"VIOX SPD\" width=\"800\" height=\"776\" srcset=\"https:\/\/test.viox.com\/wp-content\/uploads\/2025\/06\/VIOX-SPD.webp 800w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/06\/VIOX-SPD-300x291.webp 300w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/06\/VIOX-SPD-768x745.webp 768w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/06\/VIOX-SPD-12x12.webp 12w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/06\/VIOX-SPD-600x582.webp 600w\" sizes=\"(max-width: 800px) 100vw, 800px\" \/><\/p>\n<h2>Comment s\u00e9lectionner les valeurs Uc pour diff\u00e9rentes applications<\/h2>\n<h3>S\u00e9lection Uc pour les syst\u00e8mes \u00e0 tension courante<\/h3>\n<p>Voici un tableau qui montre les valeurs Uc recommand\u00e9es pour diff\u00e9rents syst\u00e8mes \u00e9lectriques :<\/p>\n<table>\n<thead>\n<tr>\n<th>Tension du syst\u00e8me<\/th>\n<th>Uc minimum requis<\/th>\n<th>Recommand\u00e9 Uc<\/th>\n<th>Marge de s\u00e9curit\u00e9<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>220 V monophas\u00e9<\/td>\n<td>255V<\/td>\n<td>275V<\/td>\n<td>25%<\/td>\n<\/tr>\n<tr>\n<td>230 V monophas\u00e9<\/td>\n<td>255V<\/td>\n<td>275V-320V<\/td>\n<td>20-39%<\/td>\n<\/tr>\n<tr>\n<td>380 V triphas\u00e9<\/td>\n<td>320 V<\/td>\n<td>385 V<\/td>\n<td>21%<\/td>\n<\/tr>\n<tr>\n<td>400 V triphas\u00e9<\/td>\n<td>460V<\/td>\n<td>500V<\/td>\n<td>25%<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<blockquote><p><strong>\ud83d\udca1 Conseil D&#039;Expert:<\/strong> Pour les syst\u00e8mes 230 V, choisissez un SPD avec une valeur nominale Uc d&#039;au moins 275 V, de nombreuses applications utilisant des valeurs Uc de 320 V \u00e0 385 V pour s&#039;adapter aux fluctuations de tension et aux d\u00e9fauts du syst\u00e8me.<\/p><\/blockquote>\n<h3>Processus de s\u00e9lection UC \u00e9tape par \u00e9tape<\/h3>\n<ol>\n<li><strong>Identifier la tension du syst\u00e8me<\/strong>\n<ul>\n<li>D\u00e9terminer la tension nominale de fonctionnement (Un)<\/li>\n<li>V\u00e9rifier la disposition de la mise \u00e0 la terre du syst\u00e8me (TN, TT, IT)<\/li>\n<li>Tenir compte des fluctuations de tension (typiquement \u00b110%)<\/li>\n<\/ul>\n<\/li>\n<li><strong>Calculer les exigences minimales en mati\u00e8re d&#039;UC<\/strong>\n<ul>\n<li>Lorsqu&#039;un d\u00e9faut \u00e0 la terre monophas\u00e9 se produit, les phases restantes subissent une tension de phase \u221a3 fois sup\u00e9rieure \u00e0 la tension normale.<\/li>\n<li>Appliquer le facteur de s\u00e9curit\u00e9 : Uc \u2265 1,3 \u00d7 Un (recommand\u00e9)<\/li>\n<\/ul>\n<\/li>\n<li><strong>S\u00e9lectionnez la valeur UC appropri\u00e9e<\/strong>\n<ul>\n<li>Choisissez parmi les valeurs standard\u00a0: 255\u00a0V, 275\u00a0V, 320\u00a0V, 385\u00a0V, 420\u00a0V<\/li>\n<li>\u00c9quilibre entre marge ad\u00e9quate et protection efficace<\/li>\n<\/ul>\n<\/li>\n<\/ol>\n<blockquote><p><strong>\u26a0\ufe0f Avertissement De S\u00e9curit\u00e9:<\/strong> Choisir une valeur Uc trop \u00e9lev\u00e9e emp\u00eache le SPD de d\u00e9marrer les actions de protection et l&#039;emp\u00eache de d\u00e9charger efficacement les courants de surtension.<\/p><\/blockquote>\n<h2>Guide de s\u00e9lection Up\u00a0: assurer une protection ad\u00e9quate de l&#039;\u00e9quipement<\/h2>\n<h3>Comprendre les exigences Up<\/h3>\n<p>Pour assurer une protection efficace, le niveau de protection en tension Up doit \u00eatre inf\u00e9rieur \u00e0 la tension de choc nominale Uw de l&#039;\u00e9quipement \u00e0 prot\u00e9ger, avec une marge de s\u00e9curit\u00e9 g\u00e9n\u00e9rale d&#039;au moins 20% (Up \u2264 0,8 \u00d7 Uw).<\/p>\n<h3>Tensions de tenue aux impulsions des \u00e9quipements<\/h3>\n<table>\n<thead>\n<tr>\n<th>Cat\u00e9gorie d&#039;\u00e9quipement<\/th>\n<th>R\u00e9sistance aux impulsions typiques (Uw)<\/th>\n<th>Requis (Max)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>\u00c9lectronique sensible<\/td>\n<td>1,5 kV<\/td>\n<td>\u2264 1,2 kV<\/td>\n<\/tr>\n<tr>\n<td>\u00c9quipement informatique standard<\/td>\n<td>2,5kV<\/td>\n<td>\u2264 2,0 kV<\/td>\n<\/tr>\n<tr>\n<td>\u00c9quipement industriel<\/td>\n<td>4,0 kV<\/td>\n<td>\u2264 3,2 kV<\/td>\n<\/tr>\n<tr>\n<td>Industrie lourde<\/td>\n<td>6,0 kV<\/td>\n<td>\u2264 4,8 kV<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Processus de s\u00e9lection<\/h3>\n<ol>\n<li><strong>D\u00e9terminer les besoins en \u00e9quipement<\/strong>\n<ul>\n<li>Identifier la tension d&#039;impulsion nominale Uw de l&#039;\u00e9quipement prot\u00e9g\u00e9<\/li>\n<li>Tenez compte des niveaux d&#039;immunit\u00e9 CEM par <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/4223\" rel=\"nofollow noopener\" target=\"_blank\">CEI 61000-4-5<\/a><\/li>\n<\/ul>\n<\/li>\n<li><strong>Appliquer des marges de s\u00e9curit\u00e9<\/strong>\n<ul>\n<li>Calculer le Up maximal autoris\u00e9 : Up \u2264 0,8 \u00d7 Uw<\/li>\n<li>Pour les installations 230\/400 V, la tension Up install\u00e9e doit g\u00e9n\u00e9ralement \u00eatre \u2264 2,5 kV<\/li>\n<\/ul>\n<\/li>\n<li><strong>Tenir compte des effets de l&#039;installation<\/strong>\n<ul>\n<li>Tenir compte des chutes de tension dans les fils de connexion<\/li>\n<li>Facteur de coordination avec les parafoudres en amont\/en aval<\/li>\n<\/ul>\n<\/li>\n<\/ol>\n<h2>Valeurs Uc et Up courantes par application<\/h2>\n<h3>Applications r\u00e9sidentielles<\/h3>\n<table>\n<thead>\n<tr>\n<th>Application<\/th>\n<th>Recommand\u00e9 Uc<\/th>\n<th>Haut typique<\/th>\n<th>Niveau de protection<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Panneau principal (230 V)<\/td>\n<td>275V<\/td>\n<td>1,5-2,5 kV<\/td>\n<td>Type 2<\/td>\n<\/tr>\n<tr>\n<td>Sous-panneaux<\/td>\n<td>275V<\/td>\n<td>1,5 kV<\/td>\n<td>Type 2<\/td>\n<\/tr>\n<tr>\n<td>\u00c9quipements sensibles<\/td>\n<td>275V<\/td>\n<td>\u2264 1,2 kV<\/td>\n<td>Type 3<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Applications commerciales\/industrielles<\/h3>\n<table>\n<thead>\n<tr>\n<th>Application<\/th>\n<th>Recommand\u00e9 Uc<\/th>\n<th>Haut typique<\/th>\n<th>Niveau de protection<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Distribution principale (400 V)<\/td>\n<td>460V<\/td>\n<td>2,5-4 kV<\/td>\n<td>Type 1+2<\/td>\n<\/tr>\n<tr>\n<td>Centres de contr\u00f4le des moteurs<\/td>\n<td>385 V<\/td>\n<td>2,5kV<\/td>\n<td>Type 2<\/td>\n<\/tr>\n<tr>\n<td>Protection des \u00e9quipements informatiques<\/td>\n<td>275V<\/td>\n<td>1,5 kV<\/td>\n<td>Type 3<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<blockquote><p><strong>\ud83d\udca1 Conseil D&#039;Expert:<\/strong> Dans les applications pratiques, les valeurs Uc de 320 V \u00e0 385 V sont g\u00e9n\u00e9ralement choisies pour les syst\u00e8mes triphas\u00e9s afin de garantir une marge ad\u00e9quate m\u00eame lorsque le SPD vieillit.<\/p><\/blockquote>\n<h2>Relation entre les valeurs Uc et Up<\/h2>\n<h3>Comment l&#039;UC affecte les performances d&#039;Up<\/h3>\n<p>La valeur Up du SPD est li\u00e9e \u00e0 la valeur Uc\u00a0; des valeurs Uc plus \u00e9lev\u00e9es entra\u00eenent g\u00e9n\u00e9ralement des valeurs Up plus \u00e9lev\u00e9es. Cette relation influence l&#039;efficacit\u00e9 de la protection\u00a0:<\/p>\n<p><strong>Relations cl\u00e9s :<\/strong><\/p>\n<ul>\n<li>Uc plus \u00e9lev\u00e9 = seuil d&#039;activation plus \u00e9lev\u00e9<\/li>\n<li>Uc plus \u00e9lev\u00e9 = valeurs Up g\u00e9n\u00e9ralement plus \u00e9lev\u00e9es<\/li>\n<li>Plus haut = Protection r\u00e9duite pour les \u00e9quipements sensibles<\/li>\n<li>Des valeurs Uc plus \u00e9lev\u00e9es entra\u00eenent une tension de d\u00e9marrage et une tension r\u00e9siduelle plus \u00e9lev\u00e9es<\/li>\n<\/ul>\n<h3>Strat\u00e9gie d&#039;optimisation<\/h3>\n<ol>\n<li><strong>S\u00e9lectionnez Uc minimum ad\u00e9quat<\/strong>\n<ul>\n<li>R\u00e9pondre aux exigences de tension du syst\u00e8me<\/li>\n<li>Tenir compte des fluctuations de tension<\/li>\n<li>\u00c9vitez les valeurs inutilement \u00e9lev\u00e9es qui compromettent la protection<\/li>\n<\/ul>\n<\/li>\n<li><strong>V\u00e9rifier la compatibilit\u00e9 Up<\/strong>\n<ul>\n<li>Assurez-vous que Up &lt; tension de tenue de l&#039;\u00e9quipement<\/li>\n<li>Tenir compte des exigences de coordination<\/li>\n<li>Tenir compte des chutes de tension de l&#039;installation<\/li>\n<\/ul>\n<\/li>\n<\/ol>\n<h2>S\u00e9lection du SPD par type de syst\u00e8me<\/h2>\n<h3>Configuration requise pour le syst\u00e8me TN<\/h3>\n<p>Pour les syst\u00e8mes TN (TN-C, TN-S, TN-CS), o\u00f9 le neutre est mis \u00e0 la terre, diff\u00e9rentes configurations de parafoudres sont requises :<\/p>\n<table>\n<thead>\n<tr>\n<th>Type De Syst\u00e8me De<\/th>\n<th>Configuration du SPD<\/th>\n<th>Uc typique<\/th>\n<th>Notes<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>TN-C<\/td>\n<td>3P (protection L-PEN)<\/td>\n<td>275V-385V<\/td>\n<td>Terre-neutre combin\u00e9<\/td>\n<\/tr>\n<tr>\n<td>TN-S<\/td>\n<td>3P+N (L-PE, N-PE)<\/td>\n<td>275V-385V<\/td>\n<td>Neutre s\u00e9par\u00e9, terre<\/td>\n<\/tr>\n<tr>\n<td>TN-CS<\/td>\n<td>3P+N au changement<\/td>\n<td>275V-385V<\/td>\n<td>Point de transition critique<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Configuration requise pour TT<\/h3>\n<p>Les syst\u00e8mes TT n\u00e9cessitent une protection contre les surtensions en mode commun et en mode diff\u00e9rentiel en raison de l&#039;asym\u00e9trie de l&#039;imp\u00e9dance de la terre.<\/p>\n<h3>Configuration requise du syst\u00e8me informatique<\/h3>\n<p>Les syst\u00e8mes informatiques ne disposent pas de connexion directe \u00e0 la terre ni de connexion \u00e0 la terre \u00e0 haute imp\u00e9dance, ce qui permet un fonctionnement continu en cas de d\u00e9faut \u00e0 la terre unique.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-16658\" src=\"https:\/\/test.viox.com\/wp-content\/uploads\/2025\/05\/Different-varieties-and-colors-of-SPDs-are-displayed-on-the-wall.webp\" alt=\"Different varieties and colors of SPDs are displayed on the wall.\" width=\"800\" height=\"684\" srcset=\"https:\/\/test.viox.com\/wp-content\/uploads\/2025\/05\/Different-varieties-and-colors-of-SPDs-are-displayed-on-the-wall.webp 800w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/05\/Different-varieties-and-colors-of-SPDs-are-displayed-on-the-wall-300x257.webp 300w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/05\/Different-varieties-and-colors-of-SPDs-are-displayed-on-the-wall-768x657.webp 768w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/05\/Different-varieties-and-colors-of-SPDs-are-displayed-on-the-wall-14x12.webp 14w, https:\/\/test.viox.com\/wp-content\/uploads\/2025\/05\/Different-varieties-and-colors-of-SPDs-are-displayed-on-the-wall-600x513.webp 600w\" sizes=\"(max-width: 800px) 100vw, 800px\" \/><\/p>\n<h2>D\u00e9pannage des probl\u00e8mes courants li\u00e9s aux UC et UP<\/h2>\n<h3>Probl\u00e8me\u00a0: le SPD ne s&#039;active pas pendant les surtensions<\/h3>\n<p><strong>Causes possibles\u00a0:<\/strong><\/p>\n<ul>\n<li>La valeur Uc choisie est trop \u00e9lev\u00e9e pour les conditions du syst\u00e8me<\/li>\n<li>\u00c9valuation incorrecte de la mise \u00e0 la terre du syst\u00e8me<\/li>\n<li>D\u00e9gradation du SPD au fil du temps<\/li>\n<\/ul>\n<p><strong>Solutions:<\/strong><\/p>\n<ol>\n<li>Recalculer les tensions du syst\u00e8me, y compris les conditions de d\u00e9faut<\/li>\n<li>S\u00e9lectionnez une valeur Uc inf\u00e9rieure dans la plage de fonctionnement s\u00fbre<\/li>\n<li>V\u00e9rifier le type et la configuration du syst\u00e8me de mise \u00e0 la terre<\/li>\n<\/ol>\n<h3>Probl\u00e8me\u00a0: \u00e9quipement endommag\u00e9 malgr\u00e9 l&#039;installation du SPD<\/h3>\n<p><strong>Causes possibles\u00a0:<\/strong><\/p>\n<ul>\n<li>La valeur Up d\u00e9passe la tension de tenue de l&#039;\u00e9quipement<\/li>\n<li>Coordination inad\u00e9quate entre les niveaux du SPD<\/li>\n<li>Mauvaise installation ou mise \u00e0 la terre du SPD<\/li>\n<\/ul>\n<p><strong>Solutions:<\/strong><\/p>\n<ol>\n<li>Assurez-vous que Up \u2264 0,8 \u00d7 tension de tenue aux impulsions de l&#039;\u00e9quipement<\/li>\n<li>Installer un syst\u00e8me SPD coordonn\u00e9 \u00e0 plusieurs niveaux<\/li>\n<li>V\u00e9rifier les connexions \u00e0 la terre \u00e0 faible r\u00e9sistance<\/li>\n<\/ol>\n<h3>Probl\u00e8me\u00a0: remplacement fr\u00e9quent du SPD<\/h3>\n<p><strong>Causes possibles\u00a0:<\/strong><\/p>\n<ul>\n<li>Valeur Uc trop proche de la tension de fonctionnement du syst\u00e8me<\/li>\n<li>Surtensions temporaires excessives<\/li>\n<li>D\u00e9gradation de l&#039;environnement<\/li>\n<\/ul>\n<p><strong>Solutions:<\/strong><\/p>\n<ol>\n<li>Augmenter la marge de s\u00e9curit\u00e9 Uc<\/li>\n<li>R\u00e9soudre les probl\u00e8mes de qualit\u00e9 de l&#039;\u00e9nergie en amont<\/li>\n<li>Mettre en \u0153uvre un programme d&#039;entretien r\u00e9gulier<\/li>\n<\/ol>\n<h2>Exigences de s\u00e9curit\u00e9 et conformit\u00e9 au code<\/h2>\n<h3>Exigences de la norme CEI<\/h3>\n<p><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/5682\" rel=\"nofollow noopener\" target=\"_blank\">IEC 61643-11<\/a> sp\u00e9cifie les exigences relatives aux SPD dans les syst\u00e8mes de distribution basse tension, tandis que la norme IEC 62305-4 traite des exigences relatives aux syst\u00e8mes de protection contre la foudre.<\/p>\n<p><strong>Exigences cl\u00e9s en mati\u00e8re de s\u00e9curit\u00e9 :<\/strong><\/p>\n<ul>\n<li>Parafoudre de type 1 avec Iimp \u2265 12,5 kA pour installations avec syst\u00e8mes de protection contre la foudre<\/li>\n<li>Parafoudre de type 2 avec In \u2265 5 kA pour installations CA standard<\/li>\n<li>Une bonne coordination entre les niveaux de protection<\/li>\n<\/ul>\n<h3>Consignes de s\u00e9curit\u00e9 d&#039;installation<\/h3>\n<p><strong>\u26a0\ufe0f Points de s\u00e9curit\u00e9 critiques :<\/strong><\/p>\n<ul>\n<li>L&#039;installation doit \u00eatre effectu\u00e9e par des \u00e9lectriciens certifi\u00e9s<\/li>\n<li>Une mise \u00e0 la terre ad\u00e9quate est essentielle au fonctionnement du SPD<\/li>\n<li>Inspection et entretien r\u00e9guliers requis<\/li>\n<li>Les SPD doivent inclure des fonctions d&#039;indication de d\u00e9faillance<\/li>\n<\/ul>\n<h2>Conseils de s\u00e9lection d&#039;experts<\/h2>\n<h3>Recommandations Professionnelles<\/h3>\n<ol>\n<li><strong>Choisissez toujours des SPD certifi\u00e9s<\/strong>\n<ul>\n<li>S\u00e9lectionnez des SPD certifi\u00e9s UL ou IEC aupr\u00e8s d&#039;installations de test r\u00e9put\u00e9es<\/li>\n<li>V\u00e9rifier la conformit\u00e9 aux codes \u00e9lectriques locaux<\/li>\n<\/ul>\n<\/li>\n<li><strong>Tenir compte des performances \u00e0 long terme<\/strong>\n<ul>\n<li>S\u00e9lectionnez les valeurs Uc avec une marge ad\u00e9quate pour tenir compte du vieillissement<\/li>\n<li>Choisissez des cotes plus \u00e9lev\u00e9es pour une dur\u00e9e de vie plus longue du SPD<\/li>\n<\/ul>\n<\/li>\n<li><strong>Plan de coordination<\/strong>\n<ul>\n<li>Plusieurs dispositifs SPD doivent \u00eatre coordonn\u00e9s conform\u00e9ment au r\u00e8glement 534.4.4.5<\/li>\n<li>Envisager une coordination \u00e9nerg\u00e9tique entre les niveaux de protection<\/li>\n<\/ul>\n<\/li>\n<li><strong>Tenir compte des changements futurs<\/strong>\n<ul>\n<li>Conception pour les modifications potentielles de la tension du syst\u00e8me<\/li>\n<li>Envisager des mises \u00e0 niveau de l\u2019\u00e9quipement et des changements de sensibilit\u00e9<\/li>\n<\/ul>\n<\/li>\n<\/ol>\n<blockquote><p><strong>\ud83d\udca1 Conseil D&#039;Expert:<\/strong> La s\u00e9lection de courants de surtension plus \u00e9lev\u00e9s n&#039;offre pas toujours une meilleure protection, mais offre une dur\u00e9e de vie plus longue du SPD.<\/p><\/blockquote>\n<h2>Foire Aux Questions<\/h2>\n<h3>Que se passe-t-il si Uc est trop faible pour mon syst\u00e8me ?<\/h3>\n<p>Si la tension Uc est inf\u00e9rieure \u00e0 la tension de fonctionnement du syst\u00e8me, le parafoudre s&#039;active en continu, entra\u00eenant une panne imm\u00e9diate et des risques potentiels pour la s\u00e9curit\u00e9. Assurez-vous toujours que la tension Uc est sup\u00e9rieure \u00e0 la tension maximale pr\u00e9vue du syst\u00e8me.<\/p>\n<h3>Puis-je utiliser un SPD avec une valeur Up sup\u00e9rieure \u00e0 la valeur nominale de mon \u00e9quipement ?<\/h3>\n<p>Non, la valeur Up doit \u00eatre inf\u00e9rieure \u00e0 la tension de tenue aux chocs de votre \u00e9quipement, avec une marge de s\u00e9curit\u00e9 d&#039;au moins 20% (Up \u2264 0,8 \u00d7 Uw). Des valeurs Up sup\u00e9rieures peuvent permettre \u00e0 des tensions dangereuses d&#039;atteindre votre \u00e9quipement.<\/p>\n<h3>Comment d\u00e9terminer la tension de tenue aux chocs de mon \u00e9quipement ?<\/h3>\n<p>V\u00e9rifiez les sp\u00e9cifications de l&#039;\u00e9quipement concernant la tension d&#039;impulsion nominale (Uw) ou la cat\u00e9gorie de surtension. La plupart des \u00e9quipements sensibles des installations 230\/400 V doivent \u00eatre prot\u00e9g\u00e9s contre les surtensions de cat\u00e9gorie II (2,5 kV).<\/p>\n<h3>Dois-je choisir la valeur Uc la plus \u00e9lev\u00e9e disponible pour une s\u00e9curit\u00e9 maximale ?<\/h3>\n<p>Non, des valeurs Uc plus \u00e9lev\u00e9es ne sont pas toujours meilleures. Une valeur Uc plus \u00e9lev\u00e9e entra\u00eene une tension de d\u00e9marrage et une tension r\u00e9siduelle plus \u00e9lev\u00e9es, ce qui peut compromettre l&#039;efficacit\u00e9 de la protection. Choisissez la valeur Uc optimale en fonction des exigences de votre syst\u00e8me.<\/p>\n<h3>\u00c0 quelle fr\u00e9quence les SPD doivent-ils \u00eatre inspect\u00e9s ?<\/h3>\n<p>Une inspection r\u00e9guli\u00e8re est essentielle, les parafoudres pr\u00e9sentant des indicateurs non fonctionnels n\u00e9cessitant un remplacement imm\u00e9diat. Pr\u00e9voyez des inspections annuelles ou apr\u00e8s des surtensions importantes.<\/p>\n<h3>Quelle est la diff\u00e9rence entre les SPD de type 1, de type 2 et de type 3\u00a0?<\/h3>\n<p>Les SPD de type 1 g\u00e8rent les coups de foudre directs (10\/350 \u00b5s), les SPD de type 2 assurent la protection de l&#039;installation principale (8\/20 \u00b5s) et les SPD de type 3 prot\u00e8gent les \u00e9quipements individuels \u00e0 proximit\u00e9 des charges.<\/p>\n<h2>Conclusion : faire le bon choix<\/h2>\n<p>La compr\u00e9hension des param\u00e8tres Uc et Up est essentielle pour une protection efficace contre les surtensions. Des valeurs Uc correctement s\u00e9lectionn\u00e9es garantissent le bon fonctionnement des parafoudres en cas de surtension, tandis que des valeurs Up correctes garantissent une protection ad\u00e9quate des \u00e9quipements.<\/p>\n<p><strong>Points cl\u00e9s \u00e0 retenir pour une s\u00e9lection optimale\u00a0:<\/strong><\/p>\n<ul>\n<li>Choisissez Uc avec une marge de s\u00e9curit\u00e9 ad\u00e9quate au-dessus de la tension du syst\u00e8me<\/li>\n<li>Assurez-vous que Up reste en dessous de la capacit\u00e9 de r\u00e9sistance de l&#039;\u00e9quipement<\/li>\n<li>Tenir compte de la disposition de la mise \u00e0 la terre du syst\u00e8me et des conditions de d\u00e9faut<\/li>\n<li>Mettre en \u0153uvre une protection coordonn\u00e9e \u00e0 plusieurs niveaux<\/li>\n<li>Privil\u00e9giez les parafoudres certifi\u00e9s avec une installation appropri\u00e9e<\/li>\n<\/ul>\n<p>Pour les installations complexes ou les applications critiques, consultez des ing\u00e9nieurs \u00e9lectriciens qualifi\u00e9s afin de garantir un choix optimal de parafoudres et une protection optimale du syst\u00e8me. L&#039;investissement dans une protection contre les surtensions ad\u00e9quate est largement sup\u00e9rieur au co\u00fbt de remplacement des \u00e9quipements endommag\u00e9s et aux temps d&#039;arr\u00eat du syst\u00e8me.<\/p>\n<h2>Li\u00e9es<\/h2>\n<p><a href=\"https:\/\/test.viox.com\/fr\/what-is-a-surge-protection-device\/\">Qu&#039;est-ce qu&#039;un dispositif de protection contre les surtensions (SPD)<\/a><\/p>\n<p><a href=\"https:\/\/test.viox.com\/fr\/how-surge-protection-devices-divert-and-limit-transient-voltages-for-safety-and-reliability\/\">Comment les parafoudres d\u00e9tournent ou limitent les tensions transitoires pour garantir la s\u00e9curit\u00e9 et la fiabilit\u00e9<\/a><\/p>\n<p><a href=\"https:\/\/test.viox.com\/fr\/how-to-choose-the-right-spd-for-your-solar-power-system\/\">Comment choisir le bon SPD pour votre syst\u00e8me d'\u00e9nergie solaire ?<\/a><\/p>\n<p><a href=\"https:\/\/test.viox.com\/fr\/why-we-use-ac-in-home-not-dc\/\">Pourquoi utiliser le courant alternatif \u00e0 la maison et non le courant continu<\/a><\/p>\n<p><a href=\"https:\/\/test.viox.com\/fr\/surge-protective-device-type-1-vs-type-2-vs-type-3\/\">Dispositif de protection contre les surtensions Type 1 vs Type 2 vs Type 3<\/a><\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>Uc and Up are two critical voltage parameters that determine how effectively a Surge Protection Device (SPD) will protect your electrical equipment. Uc represents the maximum continuous operating voltage, while Up indicates the voltage protection level that limits surge voltage during activation. Understanding these parameters correctly ensures optimal surge protection and prevents costly equipment damage. [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":18718,"comment_status":"closed","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"inline_featured_image":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"footnotes":""},"categories":[1],"tags":[],"class_list":["post-18696","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"_links":{"self":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/posts\/18696","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/comments?post=18696"}],"version-history":[{"count":0,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/posts\/18696\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/media\/18718"}],"wp:attachment":[{"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/media?parent=18696"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/categories?post=18696"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/test.viox.com\/fr\/wp-json\/wp\/v2\/tags?post=18696"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}