{"id":21474,"date":"2026-01-28T18:23:42","date_gmt":"2026-01-28T10:23:42","guid":{"rendered":"https:\/\/viox.com\/?p=21474"},"modified":"2026-01-28T18:23:46","modified_gmt":"2026-01-28T10:23:46","slug":"mccb-short-time-delay-icw-rating-explained","status":"publish","type":"post","link":"https:\/\/test.viox.com\/de\/mccb-short-time-delay-icw-rating-explained\/","title":{"rendered":"Warum bieten Kompaktleistungsschalter (MCCBs) einen kurzzeitverz\u00f6gerten Schutz ohne eine Bemessungskurzzeitstromfestigkeit (I<sub>cw<\/sub>)"},"content":{"rendered":"<div class=\"product-intro\">\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/MCCB-electronic-trip-unit-in-industrial-panel-showing-400A-rating-and-current-display.webp\" alt=\"MCCB electronic trip unit in industrial panel showing 400A rating and current display - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">Elektronischer Ausl\u00f6ser eines MCCB in einem Industrieschrank mit Anzeige von 400A Nennstrom und Stromanzeige \u2013 VIOX Electric<\/figcaption><\/figure>\n<h2>Direkte Antwort<\/h2>\n<p><strong><a href=\"https:\/\/test.viox.com\/de\/mccb\/\">Molded Case Circuit Breakers (MCCBs)<\/a> k\u00f6nnen einen Kurzzeitverz\u00f6gerungsschutz ohne einen Bemessungskurzzeitstrom (I<sub>cw<\/sub>) bieten, da sie zur IEC 60947-2 Kategorie A geh\u00f6ren, bei der die Selektivit\u00e4t durch strombegrenzende Technologie und nicht durch absichtliche Zeitverz\u00f6gerungen erreicht wird.<\/strong> Im Gegensatz zu Leistungsschaltern (ACBs) der Kategorie B, die Fehlerstr\u00f6me mit hohen I<sub>cw<\/sub> -Werten \"aussitzen\", nutzen MCCBs elektromagnetische Kontaktabsto\u00dfung und ultraschnelle Lichtbogenunterbrechung, um die Fehlerenergie zu begrenzen \u2013 sie sch\u00fctzen sich selbst und koordinieren sich dennoch mit nachgeschalteten Ger\u00e4ten durch ihre inh\u00e4renten Kurzzeitverz\u00f6gerungseigenschaften (typischerweise 10-12\u00d7 I<sub>n<\/sub>) unterhalb der Ansprechschwelle des unverz\u00f6gerten Ausl\u00f6sers.<\/p>\n<hr \/>\n<h2>Wichtigste Erkenntnisse<\/h2>\n<ul>\n<li>\u2705 <strong>Kategorie A vs. B<\/strong>: MCCBs (Kategorie A) haben keine deklarierten I<sub>cw<\/sub> -Werte, besitzen aber eine inh\u00e4rente Kurzzeitfestigkeit unterhalb ihrer Kontaktabsto\u00dfungsschwelle (typischerweise &gt;12-14\u00d7 I<sub>n<\/sub>)<\/li>\n<li>\u2705 <strong>Strombegrenzende Physik<\/strong>: Der Kontaktfederdruck ist in MCCBs absichtlich niedrig, um eine schnelle elektromagnetische Absto\u00dfung bei hohen Fehlerstr\u00f6men (&gt;25\u00d7 I<sub>n<\/sub>) zu erm\u00f6glichen, wodurch Sch\u00e4den durch schnelle Unterbrechung und nicht durch l\u00e4ngere Festigkeit verhindert werden<\/li>\n<li>\u2705 <strong>Kurzzeitverz\u00f6gerungs-Realit\u00e4t<\/strong>: MCCB-Kurzzeitverz\u00f6gerungseinstellungen (z. B. 10\u00d7 I<sub>n<\/sub>, 0,4s) funktionieren nur, wenn der Fehlerstrom unterhalb der Ansprechschwelle des unverz\u00f6gerten Ausl\u00f6sers bleibt \u2013 wird diese \u00fcberschritten, wird sofort \u00fcber magnetischen Ausl\u00f6ser oder energiebasierte Mechanismen reagiert<\/li>\n<li>\u2705 <strong>Selektivit\u00e4tsbeschr\u00e4nkungen<\/strong>: Volle Selektivit\u00e4t zwischen MCCBs erfordert sorgf\u00e4ltige Koordinationstabellen; ACB-zu-MCCB-Kaskaden erzielen bessere Ergebnisse, da ACBs wirklich verz\u00f6gern k\u00f6nnen (I<sub>cw<\/sub> = I<sub>Icu<\/sub> -F\u00e4higkeit), w\u00e4hrend MCCBs nachgeschaltete Fehler behandeln<\/li>\n<li>\u2705 <strong>Sicherheits\u00fcbersteuerung<\/strong>: Fortschrittliche MCCBs mit deaktivierbaren unverz\u00f6gerten Ausl\u00f6sern (z. B. Schneider NSX) verf\u00fcgen \u00fcber \u201cEnergieausl\u00f6ser\u201d- oder \u201cunverz\u00f6gerte \u00dcbersteuerungs\u201d-Funktionen \u2013 wenn der Fehlerstrom ~25\u00d7 I<sub>n<\/sub>, \u00fcberschreitet, erzwingen gasbet\u00e4tigte Mechanismen eine sofortige Ausl\u00f6sung unabh\u00e4ngig von den Einstellungen<\/li>\n<\/ul>\n<hr \/>\n<h2>Verst\u00e4ndnis der Selektivit\u00e4tskategorien nach IEC 60947-2<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/Size-and-construction-comparison-between-ACB-with-Icw-rating-and-compact-MCCB-Category-A-breaker.webp\" alt=\"Size and construction comparison between ACB with Icw rating and compact MCCB Category A breaker - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">Gr\u00f6\u00dfen- und Konstruktionsvergleich zwischen ACB mit Icw-Wert und kompaktem MCCB-Schutzschalter der Kategorie A \u2013 VIOX Electric<\/figcaption><\/figure>\n<h3>Kategorie B: ACBs mit deklariertem I<sub>cw<\/sub><\/h3>\n<p>Leistungsschalter (ACBs) sind ausgelegt f\u00fcr <strong>Kategorie B<\/strong> Anwendungen, bei denen die Selektivit\u00e4t durch absichtliche Kurzzeitverz\u00f6gerungen erreicht wird. Gem\u00e4\u00df IEC 60947-2 m\u00fcssen diese Ger\u00e4te einen Bemessungskurzzeitstrom (I<sub>cw<\/sub>) angeben \u2013 den maximalen Fehlerstrom, den der Schalter in geschlossener Position f\u00fcr eine bestimmte Dauer (0,05s, 0,1s, 0,25s, 0,5s oder 1,0s) f\u00fchren kann, ohne Schaden zu nehmen.<\/p>\n<p><strong>Hauptmerkmale von Schutzschaltern der Kategorie B:<\/strong><\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Parameter<\/th>\n<th>Spezifikation<\/th>\n<th>Zweck<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>Ich<sub>cw<\/sub> Bewertung<\/strong><\/td>\n<td>Mindestens 12\u00d7 I<sub>n<\/sub> oder 5kA (\u22642500A Baugr\u00f6\u00dfen)<br \/>\nMindestens 30kA (&gt;2500A Baugr\u00f6\u00dfen)<\/td>\n<td>Erm\u00f6glicht absichtliche Verz\u00f6gerung bei Fehlern<\/td>\n<\/tr>\n<tr>\n<td><strong>Kontakt Design<\/strong><\/td>\n<td>Hoher Federdruck<\/td>\n<td>Verhindert Kontaktabsto\u00dfung w\u00e4hrend der Verz\u00f6gerungszeit<\/td>\n<\/tr>\n<tr>\n<td><strong>Ausl\u00f6severz\u00f6gerung<\/strong><\/td>\n<td>Unverz\u00f6gerter Ausl\u00f6ser kann deaktiviert werden<\/td>\n<td>Erm\u00f6glicht reine zeitbasierte Koordination<\/td>\n<\/tr>\n<tr>\n<td><strong>Typische Anwendung<\/strong><\/td>\n<td>Haupteinspeisungen, Verteilungsabg\u00e4nge<\/td>\n<td>Koordiniert mit nachgeschalteten MCCBs<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Beispielsweise kann ein 800A ACB mit I<sub>cw<\/sub> = 85kA\/1s einem Fehlerstrom von 85kA bis zu 1 Sekunde standhalten, w\u00e4hrend das Kurzzeitverz\u00f6gerungsrelais \u201cwartet\u201d, bis nachgeschaltete Ger\u00e4te den Fehler beseitigen. Diese F\u00e4higkeit erfordert eine robuste mechanische Konstruktion \u2013 verst\u00e4rkte Kontaktarme, hoher Kontaktdruck (der elektromagnetische Absto\u00dfung verhindert) und thermische Masse zur Absorption von I<sup>2<\/sup>t-Energie.<\/p>\n<h3>Kategorie A: MCCBs ohne deklarierten I<sub>cw<\/sub><\/h3>\n<p>Kompaktleistungsschalter (MCCBs) fallen typischerweise unter <strong>Kategorie A<\/strong>\u2013 Ger\u00e4te, die \u201cnicht speziell f\u00fcr die Selektivit\u00e4t unter Kurzschlussbedingungen vorgesehen sind\u201d gem\u00e4\u00df IEC 60947-2. Diese Schutzschalter deklarieren keine I<sub>cw<\/sub> -Werte, da ihre Designphilosophie <strong>schnelle Fehlerunterbrechung<\/strong> gegen\u00fcber l\u00e4ngerer Fehlerfestigkeit priorisiert.<\/p>\n<p><strong>Warum MCCBs keine I<sub>cw<\/sub>:<\/strong><\/p>\n<ol>\n<li><strong>deklarieren<\/strong>Strombegrenzendes Design<sub>n<\/sub><\/li>\n<li><strong>: Der Kontaktfederdruck ist absichtlich niedrig, um eine schnelle elektromagnetische Absto\u00dfung zu erm\u00f6glichen, wenn der Fehlerstrom ~10-14\u00d7 I<\/strong>\u00fcberschreitet<\/li>\n<li><strong>Unverz\u00f6gerte Ausl\u00f6sepflicht<\/strong>: Die meisten MCCBs k\u00f6nnen den unverz\u00f6gerten Schutz nicht deaktivieren \u2013 jeder Fehler, der die unverz\u00f6gerte Schwelle \u00fcberschreitet, l\u00f6st eine sofortige Ausl\u00f6sung aus<sup>2<\/sup>Thermische Einschr\u00e4nkungen<\/li>\n<\/ol>\n<p>: Die kompakte, vergossene Konstruktion kann die thermische Energie (I <strong>nicht<\/strong> t) nicht ableiten, die mit einer l\u00e4ngeren Hochstromfestigkeit verbunden ist.<\/p>\n<hr \/>\n<h2>Dies bedeutet jedoch nicht<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/MCCB-electromagnetic-contact-repulsion-mechanism-diagram-showing-force-balance-and-current-thresholds.webp\" alt=\"MCCB electromagnetic contact repulsion mechanism diagram showing force balance and current thresholds - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">, dass MCCBs \u00fcberhaupt keine Kurzzeitfestigkeit besitzen \u2013 sie besitzen eine inh\u00e4rente, nicht deklarierte Schwelle, unterhalb derer die Kontakte geschlossen bleiben.<\/figcaption><\/figure>\n<h3>Die Physik der MCCB-Kontaktabsto\u00dfung<\/h3>\n<p>MCCB-Diagramm des elektromagnetischen Kontaktabsto\u00dfungsmechanismus mit Darstellung des Kr\u00e4ftegleichgewichts und der Stromschwellenwerte \u2013 VIOX Electric <strong>elektrodynamische Absto\u00dfungskr\u00e4fte<\/strong> (Lorentzkraft). Die Kontaktfeder muss dieser Kraft entgegenwirken, um die Kontakte geschlossen zu halten.<\/p>\n<p><strong>Kraftbilanzgleichung:<\/strong><\/p>\n<p style=\"text-align: center; background-color: #f9f9f9; padding: 10px; border-radius: 4px;\">F<sub>Feder<\/sub> &gt; F<sub>Absto\u00dfung<\/sub> = k \u00b7 I<sup>2<\/sup><\/p>\n<p>Wo:<\/p>\n<ul>\n<li>F<sub>Feder<\/sub> = Kontaktfeder-Druckkraft<\/li>\n<li>F<sub>Absto\u00dfung<\/sub> = Elektromagnetische Absto\u00dfungskraft (proportional zu I<sup>2<\/sup>)<\/li>\n<li>k = Geometrische Konstante (Kontaktabstand, Leiterkonfiguration)<\/li>\n<\/ul>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>MCCB-Designparameter<\/th>\n<th>Kategorie A (MCCB)<\/th>\n<th>Kategorie B (ACB)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>Kontaktfederdruck<\/strong><\/td>\n<td>Niedrig (2-5 N\/mm)<\/td>\n<td>Hoch (10-20 N\/mm)<\/td>\n<\/tr>\n<tr>\n<td><strong>Absto\u00dfungsschwelle<\/strong><\/td>\n<td>12-14\u00d7 I<sub>n<\/sub><\/td>\n<td>&gt;50\u00d7 I<sub>n<\/sub><\/td>\n<\/tr>\n<tr>\n<td><strong>Kontakt\u00f6ffnungsgeschwindigkeit<\/strong><\/td>\n<td>3-7 ms (ultraschnell)<\/td>\n<td>20-50 ms (kontrolliert)<\/td>\n<\/tr>\n<tr>\n<td><strong>Design Priorit\u00e4t<\/strong><\/td>\n<td>Begrenzung der Fehlerenergie (I<sup>2<\/sup>t)<\/td>\n<td>Fehlerstandzeit<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>\u00dcberlegungen zum Motorstart<\/h3>\n<p>Untersuchungen des Shanghai Electrical Research Institute an 52 Motormustern ergaben, dass das Direktanlaufverfahren (DOL) erste Spitzenanlaufstr\u00f6me von <strong>8-12\u00d7 I<sub>n<\/sub><\/strong> f\u00fcr die meisten Motoren erzeugt, wobei Ausrei\u00dfer 13\u00d7 I<sub>n<\/sub>.<\/p>\n<p><strong>erreichen. Diese Daten bestimmen die Designbeschr\u00e4nkungen f\u00fcr MCCBs:<\/strong><\/p>\n<ul>\n<li><strong>Verteiler-MCCBs<\/strong>: Unverz\u00f6gerte Ausl\u00f6sung eingestellt auf 10-12\u00d7 I<sub>n<\/sub> (darf nicht bei Kondensatoranlauf oder Transformatorzuschaltung ausl\u00f6sen)<\/li>\n<li><strong>Motorbemessungs-MCCBs<\/strong>: Unverz\u00f6gerte Ausl\u00f6sung eingestellt auf 13-14\u00d7 I<sub>n<\/sub> (muss DOL-Start \u00fcberstehen)<\/li>\n<li><strong>Kontaktabsto\u00dfungsschwelle<\/strong>: Muss die unverz\u00f6gerte Ausl\u00f6seeinstellung um eine Marge von 15-20 % \u00fcbersteigen, um ein unerw\u00fcnschtes \u00d6ffnen der Kontakte w\u00e4hrend des Anlaufvorgangs zu verhindern<\/li>\n<\/ul>\n<p><strong>Beispielrechnung f\u00fcr einen 100A motorbemessenen MCCB:<\/strong><\/p>\n<div style=\"background-color: #f5f5f5; padding: 15px; border-radius: 5px; margin: 15px 0; font-family: monospace;\">Unverz\u00f6gerte Ausl\u00f6seeinstellung: 13 \u00d7 100A = 1.300A<br \/>\nKontaktabsto\u00dfungsschwelle: 1.300A \u00d7 1,2 = 1.560A (Designziel)<br \/>\nNicht deklarierte \u201cIcw\u201d-F\u00e4higkeit: ~1.500A (unterhalb der Absto\u00dfungsschwelle)<\/div>\n<p>Diese 1.500A-Schwelle stellt die inh\u00e4rente Kurzzeitfestigkeit des MCCB dar \u2013 ausreichend f\u00fcr die Koordination mit nachgeschalteten Ger\u00e4ten im Fehlerbereich von 1.000-1.500A, aber weit unter den deklarierten I<sub>cw<\/sub> -Werten von ACBs (typischerweise 30-85kA).<\/p>\n<hr \/>\n<h2>Wie die Kurzzeitverz\u00f6gerung des MCCB tats\u00e4chlich funktioniert<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/Technical-infographic-clean-202601280514.webp\" alt=\"MCCB three-zone protection logic diagram showing overload, short-time delay, and instantaneous trip thresholds - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">MCCB-Schutzlogikdiagramm mit drei Zonen, das \u00dcberlast-, Kurzzeitverz\u00f6gerungs- und unverz\u00f6gerte Ausl\u00f6seschwellen zeigt \u2013 VIOX Electric<\/figcaption><\/figure>\n<h3>Die drei Betriebszonen<\/h3>\n<p>Moderne elektronische MCCBs verf\u00fcgen \u00fcber drei Schutzzonen, deren Zusammenspiel sich jedoch grundlegend von ACBs unterscheidet:<\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Schutzzone<\/th>\n<th>Einstellbereich<\/th>\n<th>Tats\u00e4chliches Verhalten<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>Langzeit (\u00dcberlast)<\/strong><\/td>\n<td>0,4-1,0\u00d7 I<sub>n<\/sub>, 3-30s<\/td>\n<td>Thermischer Schutz \u00fcber I<sup>2<\/sup>t-Berechnung<\/td>\n<\/tr>\n<tr>\n<td><strong>Kurzzeitverz\u00f6gerung<\/strong><\/td>\n<td>2-12\u00d7 I<sub>n<\/sub>, 0,1-0,5s<\/td>\n<td><strong>Nur aktiv unterhalb der unverz\u00f6gerten Schwelle<\/strong><\/td>\n<\/tr>\n<tr>\n<td><strong>Unmittelbar<\/strong><\/td>\n<td>10-14\u00d7 I<sub>n<\/sub> (fest oder einstellbar)<\/td>\n<td><strong>Kann bei den meisten MCCBs nicht deaktiviert werden<\/strong><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>Szenario 1: Fehlerstrom unterhalb der unverz\u00f6gerten Schwelle<\/h3>\n<p><strong>Bedingungen<\/strong>: Fehlerstrom = 8\u00d7 I<sub>n<\/sub> (800A f\u00fcr einen 100A-Schalter)<\/p>\n<ol>\n<li>Strom \u00fcberschreitet die Langzeitzone \u2192 Kurzzeitverz\u00f6gerung wird aktiviert<\/li>\n<li>Elektronische Ausl\u00f6seeinheit startet Countdown (z.B. 0,4s)<\/li>\n<li>Wenn der Fehler weiterhin besteht, wird die Ausl\u00f6sespule nach einer Verz\u00f6gerung erregt<\/li>\n<li>Kontakte \u00f6ffnen \u00fcber einen Energiespeichermechanismus (~20-30 ms \u00d6ffnungszeit)<\/li>\n<\/ol>\n<p><strong>Ergebnis<\/strong>: Echte zeitverz\u00f6gerte Koordination mit nachgeschalteten Ger\u00e4ten<\/p>\n<h3>Szenario 2: Fehlerstrom \u00fcber dem unverz\u00f6gerten Schwellwert<\/h3>\n<p><strong>Bedingungen<\/strong>: Fehlerstrom = 15\u00d7 I<sub>n<\/sub> (1.500A f\u00fcr einen 100A Schutzschalter)<\/p>\n<ol>\n<li>Strom \u00fcberschreitet den unverz\u00f6gerten Schwellwert \u2192 Magnetische Ausl\u00f6sung erfolgt sofort<\/li>\n<li>Kurzzeit-Verz\u00f6gerungseinstellung ist <strong>\u00fcberbr\u00fcckt<\/strong><\/li>\n<li>Ausl\u00f6sespule wird innerhalb von 5-10 ms erregt<\/li>\n<li>Kontakte \u00f6ffnen, aber der Fehlerstrom hat m\u00f6glicherweise bereits elektromagnetische Absto\u00dfung verursacht<\/li>\n<\/ol>\n<p><strong>Ergebnis<\/strong>: Keine absichtliche Verz\u00f6gerung \u2013 MCCB l\u00f6st so schnell wie m\u00f6glich aus<\/p>\n<h3>Szenario 3: Fehlerstrom \u00fcbersteigt den Absto\u00dfungsschwellwert bei weitem<\/h3>\n<p><strong>Bedingungen<\/strong>: Fehlerstrom = 50\u00d7 I<sub>n<\/sub> (5.000A f\u00fcr einen 100A Schutzschalter, Ann\u00e4herung an I<sub>Icu<\/sub>)<\/p>\n<ol>\n<li>Elektromagnetische Absto\u00dfungskraft \u00fcbersteigt den Federdruck<\/li>\n<li>Kontakte werden innerhalb von 3-7 ms auseinandergetrieben (schneller als der Ausl\u00f6semechanismus)<\/li>\n<li>Lichtbogenspannung steigt schnell an und begrenzt den Spitzenstrom (strombegrenzende Wirkung)<\/li>\n<li>Lichtbogenenergie kann den Ausl\u00f6semechanismus ausl\u00f6sen, oder der Schutzschalter verl\u00e4sst sich allein auf die Lichtbogenl\u00f6schung<\/li>\n<\/ol>\n<p><strong>Ergebnis<\/strong>: Ultraschnelle Strombegrenzung \u2013 keine Koordination, aber Ger\u00e4teschutz \u00fcber I<sup>2<\/sup>t-Reduktion<\/p>\n<hr \/>\n<h2>Sonderfall: MCCBs mit deaktivierbarer unverz\u00f6gerter Ausl\u00f6sung<\/h2>\n<h3>Schneider NSX \u201cEnergy Trip\u201d-Mechanismus<\/h3>\n<p>Einige High-End-MCCBs (z. B. Schneider Electric NSX mit Micrologic-Ausl\u00f6seeinheiten) erm\u00f6glichen die Deaktivierung des unverz\u00f6gerten Schutzes f\u00fcr eine verbesserte Selektivit\u00e4t. Diese Ger\u00e4te verf\u00fcgen jedoch \u00fcber eine <strong>obligatorische Sicherheits\u00fcbersteuerung<\/strong> namens \u201cEnergy Trip\u201d oder \u201cunverz\u00f6gerte \u00dcbersteuerung\u201d.\u201d<\/p>\n<p><strong>Dr\u00e4hte in Ihrer Wand<\/strong><\/p>\n<ol>\n<li>Benutzer deaktiviert die unverz\u00f6gerte Ausl\u00f6sung, aktiviert die Kurzzeitverz\u00f6gerung (z. B. 10\u00d7 I<sub>n<\/sub>, 0,4s)<\/li>\n<li>Fehlerstrom erreicht 30\u00d7 I<sub>n<\/sub> (3.000A f\u00fcr einen 100A Schutzschalter)<\/li>\n<li>Kontakte sto\u00dfen sich ab, Lichtbogen bildet sich<\/li>\n<li>Lichtbogenenergie ionisiert gaserzeugendes Material in der Lichtbogenkammer<\/li>\n<li>Druckanstieg bet\u00e4tigt den pneumatischen Ausl\u00f6semechanismus innerhalb von 10-15 ms<\/li>\n<li>Schutzschalter l\u00f6st aus <strong>unabh\u00e4ngig von den Einstellungen der elektronischen Ausl\u00f6seeinheit<\/strong><\/li>\n<\/ol>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Fehlerstrompegel<\/th>\n<th>NSX-Reaktion<\/th>\n<th>Standard-MCCB-Reaktion<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>8\u00d7 I<sub>n<\/sub><\/strong><\/td>\n<td>Kurzzeitverz\u00f6gerung funktioniert normal<\/td>\n<td>Kurzzeitverz\u00f6gerung funktioniert<\/td>\n<\/tr>\n<tr>\n<td><strong>15\u00d7 I<sub>n<\/sub><\/strong><\/td>\n<td>Kurzzeitverz\u00f6gerung funktioniert (unverz\u00f6gert deaktiviert)<\/td>\n<td>Unverz\u00f6gerte Ausl\u00f6sung (kann nicht deaktiviert werden)<\/td>\n<\/tr>\n<tr>\n<td><strong>&gt;25\u00d7 I<sub>n<\/sub><\/strong><\/td>\n<td>Energy Trip \u00fcbersteuert die Verz\u00f6gerung<\/td>\n<td>Kontaktabsto\u00dfung + unverz\u00f6gerte Ausl\u00f6sung<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Dieses Design verhindert katastrophale Ausf\u00e4lle, wenn Benutzer die Schutzeinstellungen falsch konfigurieren \u2013 der MCCB sch\u00fctzt sich bei extremen Fehlerstr\u00f6men immer selbst, auch wenn dies die Selektivit\u00e4t beeintr\u00e4chtigt.<\/p>\n<hr \/>\n<h2>Praktische Koordinationsstrategien<\/h2>\n<figure style=\"text-align: center; margin: 20px 0;\"><img decoding=\"async\" style=\"max-width: 100%; height: auto;\" src=\"https:\/\/img.viox.com\/Time-current-coordination-diagram-showing-ACB-and-MCCB-selectivity-zones-with-fault-scenario-analysis.webp\" alt=\"Time-current coordination diagram showing ACB and MCCB selectivity zones with fault scenario analysis - VIOX Electric\" \/><figcaption style=\"font-style: italic; color: #555; margin-top: 8px;\">Zeit-Strom-Koordinationsdiagramm, das ACB- und MCCB-Selektivit\u00e4tszonen mit Fehlerfallszenarioanalyse zeigt \u2013 VIOX Electric<\/figcaption><\/figure>\n<h3>Strategie 1: ACB-zu-MCCB-Kaskade (Empfohlen)<\/h3>\n<p><strong>Konfiguration:<\/strong><\/p>\n<ul>\n<li><strong>Vorgeschaltet<\/strong>: 1600A ACB, I<sub>cw<\/sub> = 65kA\/0,5s, Kurzzeitverz\u00f6gerung = 0,4s<\/li>\n<li><strong>Nachgeschaltet<\/strong>: 400A MCCB, I<sub>Icu<\/sub> = 50kA, unverz\u00f6gert = 5.000A (12,5\u00d7 I<sub>n<\/sub>)<\/li>\n<\/ul>\n<p><strong>Koordinationsanalyse:<\/strong><\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Fehlerort<\/th>\n<th>Fehlerstrom<\/th>\n<th>Upstream-ACB-Aktion<\/th>\n<th>Downstream-MCCB-Aktion<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>Nachgeschalteter Abzweig<\/strong><\/td>\n<td>8 kA<\/td>\n<td>Wartet 0,4s (innerhalb I<sub>cw<\/sub>)<\/td>\n<td>L\u00f6st sofort aus (&gt;12,5\u00d7 I<sub>n<\/sub>)<\/td>\n<\/tr>\n<tr>\n<td><strong>Nachgeschalteter Abzweig<\/strong><\/td>\n<td>45 kA<\/td>\n<td>Wartet 0,4s (innerhalb I<sub>cw<\/sub>)<\/td>\n<td>L\u00f6st sofort aus (strombegrenzend)<\/td>\n<\/tr>\n<tr>\n<td><strong>Hauptsammelschiene<\/strong><\/td>\n<td>60 kA<\/td>\n<td>L\u00f6st nach 0,4s aus<\/td>\n<td>Nicht beeinflusst<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><strong>Ergebnis<\/strong>: Volle Selektivit\u00e4t bis 50kA (MCCB I<sub>Icu<\/sub> Begrenzung)<\/p>\n<h3>Strategie 2: MCCB-zu-MCCB-Koordination (begrenzt)<\/h3>\n<p><strong>Konfiguration:<\/strong><\/p>\n<ul>\n<li><strong>Vorgeschaltet<\/strong>: 400A MCCB, unverz\u00f6gert = 5.000A (12,5\u00d7 I<sub>n<\/sub>)<\/li>\n<li><strong>Nachgeschaltet<\/strong>: 100A MCCB, unverz\u00f6gert = 1.300A (13\u00d7 I<sub>n<\/sub>)<\/li>\n<\/ul>\n<p><strong>Koordinationsanalyse:<\/strong><\/p>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Fehlerstrom<\/th>\n<th>Vorgelagerter MCCB<\/th>\n<th>Nachgelagerter MCCB<\/th>\n<th>Selektivit\u00e4t?<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>1.500 A<\/strong><\/td>\n<td>Kurzzeitverz\u00f6gerung (0,3s)<\/td>\n<td>Sofortreise<\/td>\n<td>\u2705 Jawohl<\/td>\n<\/tr>\n<tr>\n<td><strong>4.000A<\/strong><\/td>\n<td>Kurzzeitverz\u00f6gerung (0,3s)<\/td>\n<td>Sofortreise<\/td>\n<td>\u2705 Jawohl<\/td>\n<\/tr>\n<tr>\n<td><strong>6.000A<\/strong><\/td>\n<td><strong>Sofortreise<\/strong><\/td>\n<td>Sofortreise<\/td>\n<td>\u274c Nein (beide l\u00f6sen aus)<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p><strong>Selektivit\u00e4tsgrenze<\/strong>: ~4.500A (90% der unverz\u00f6gerten Einstellung des vorgeschalteten Ger\u00e4ts)<\/p>\n<p><strong>Verbesserung<\/strong>: Verwenden Sie die Koordinationstabellen des Herstellers, um die tats\u00e4chliche Durchlassenergie zu \u00fcberpr\u00fcfen \u2013 strombegrenzende MCCBs k\u00f6nnen durch I<sup>2<\/sup>t-Diskriminierung auch bei h\u00f6heren Fehlerstr\u00f6men Selektivit\u00e4t erreichen.<\/p>\n<hr \/>\n<h2>Vergleichstabelle: ACB vs. MCCB Kurzzeitverhalten<\/h2>\n<table style=\"border-collapse: collapse; width: 100%; margin: 20px 0;\" border=\"1\" cellpadding=\"10\">\n<thead>\n<tr style=\"background-color: #f2f2f2;\">\n<th>Feature<\/th>\n<th>ACB (Kategorie B)<\/th>\n<th>MCCB (Kategorie A)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td><strong>Ich<sub>cw<\/sub> Deklaration<\/strong><\/td>\n<td>\u2705 Ja (30-85 kA, 0,05-1,0s)<\/td>\n<td>\u274c Nein (nicht deklariert)<\/td>\n<\/tr>\n<tr>\n<td><strong>Eigenfestigkeit<\/strong><\/td>\n<td>Sehr hoch (&gt;50\u00d7 I<sub>n<\/sub>)<\/td>\n<td>Begrenzt (12-14\u00d7 I<sub>n<\/sub>)<\/td>\n<\/tr>\n<tr>\n<td><strong>Kontaktfederdruck<\/strong><\/td>\n<td>Hoch (verhindert Absto\u00dfung)<\/td>\n<td>Niedrig (erm\u00f6glicht Strombegrenzung)<\/td>\n<\/tr>\n<tr>\n<td><strong>Unverz\u00f6gerte Ausl\u00f6sung<\/strong><\/td>\n<td>Kann deaktiviert werden<\/td>\n<td>Normalerweise fest (kann nicht deaktiviert werden)<\/td>\n<\/tr>\n<tr>\n<td><strong>Kurzzeitverz\u00f6gerungsbereich<\/strong><\/td>\n<td>0,05-1,0s (einstellbar)<\/td>\n<td>0,1-0,5s (nur unterhalb der unverz\u00f6gerten Schwelle)<\/td>\n<\/tr>\n<tr>\n<td><strong>Koordinationsmethode<\/strong><\/td>\n<td>Zeitbasiert (echte Verz\u00f6gerung)<\/td>\n<td>Stromabh\u00e4ngig (Begrenzung + Verz\u00f6gerung)<\/td>\n<\/tr>\n<tr>\n<td><strong>Typische Anwendung<\/strong><\/td>\n<td>Haupteinspeisung (1000-6300A)<\/td>\n<td>Abgangsschutz (16-1600A)<\/td>\n<\/tr>\n<tr>\n<td><strong>Selektivit\u00e4t mit nachgeschalteten Ger\u00e4ten<\/strong><\/td>\n<td>Vollst\u00e4ndig (bis I<sub>cw<\/sub>)<\/td>\n<td>Teilweise (bis zur unverz\u00f6gerten Schwelle)<\/td>\n<\/tr>\n<tr>\n<td><strong>Selbstschutzmechanismus<\/strong><\/td>\n<td>Thermische Masse + mechanische Festigkeit<\/td>\n<td>Kontaktabsto\u00dfung + St\u00f6rlichtbogenbegrenzung<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<hr \/>\n<h2>Warum das f\u00fcr die Systemauslegung wichtig ist<\/h2>\n<h3>Missverst\u00e4ndnis 1: \u201cMCCB-Kurzzeitverz\u00f6gerung = ACB-Kurzzeitverz\u00f6gerung\u201d<\/h3>\n<p><strong>Realit\u00e4t<\/strong>: Die MCCB-Kurzzeitverz\u00f6gerung funktioniert nur in einem engen Stromfenster (zwischen Langzeit- und Unverz\u00f6gert-Schwellen). Bei Fehlern, die die unverz\u00f6gerten Einstellungen \u00fcberschreiten, l\u00f6sen MCCBs sofort aus \u2013 es tritt keine Verz\u00f6gerung auf.<\/p>\n<p><strong>Auswirkungen auf die Auslegung<\/strong>: \u00dcberpr\u00fcfen Sie bei der Spezifizierung des MCCB-Schutzes immer:<\/p>\n<ol>\n<li>Unverz\u00f6gerte Einstellungen des nachgeschalteten Ger\u00e4ts<\/li>\n<li>Maximaler Fehlerstrom am Koordinationspunkt<\/li>\n<li>Ob der Fehlerstrom die unverz\u00f6gerte Schwelle des vorgeschalteten MCCB \u00fcberschreitet<\/li>\n<\/ol>\n<h3>Missverst\u00e4ndnis 2: \u201cKein I<sub>cw<\/sub> Rating = Keine Kurzzeitf\u00e4higkeit\u201d<\/h3>\n<p><strong>Realit\u00e4t<\/strong>: MCCBs besitzen eine inh\u00e4rente Kurzzeitfestigkeit bis zu ihrer Kontaktabsto\u00dfungsschwelle (~12-14\u00d7 I<sub>n<\/sub>). Diese F\u00e4higkeit erm\u00f6glicht eine begrenzte Koordination mit nachgeschalteten Ger\u00e4ten, jedoch nicht im Umfang von ACBs.<\/p>\n<p><strong>Auswirkungen auf die Auslegung<\/strong>: Die MCCB-zu-MCCB-Koordination ist m\u00f6glich, erfordert aber:<\/p>\n<ul>\n<li>Sorgf\u00e4ltige Trennung der unverz\u00f6gerten Einstellungen (mindestens 1,5:1 Verh\u00e4ltnis)<\/li>\n<li>Vom Hersteller bereitgestellte Selektivit\u00e4tstabellen<\/li>\n<li>Ber\u00fccksichtigung der strombegrenzenden Effekte auf die Durchlassenergie<\/li>\n<\/ul>\n<h3>Missverst\u00e4ndnis 3: \u201cDeaktivieren der unverz\u00f6gerten Ausl\u00f6sung macht MCCB = ACB\u201d<\/h3>\n<p><strong>Realit\u00e4t<\/strong>: Selbst MCCBs mit deaktivierbarer unverz\u00f6gerter Ausl\u00f6sung (z. B. NSX) verf\u00fcgen \u00fcber energiebasierte Override-Mechanismen, die bei extrem hohen Fehlerstr\u00f6men (&gt;25\u00d7 I<sub>n<\/sub>) eine Ausl\u00f6sung erzwingen. Sie k\u00f6nnen hohe Fehlerstr\u00f6me nicht wie ACBs \u201caussitzen\u201d.<\/p>\n<p><strong>Auswirkungen auf die Auslegung<\/strong>: Bei der Verwendung von MCCBs mit einstellbarer unverz\u00f6gerter Ausl\u00f6sung:<\/p>\n<ul>\n<li>\u00dcberpr\u00fcfen Sie den Energieausl\u00f6seschwellwert beim Hersteller<\/li>\n<li>Gehen Sie nicht von einem ACB-\u00e4hnlichen Verhalten bei Fehlerstr\u00f6men nahe I<sub>Icu<\/sub><\/li>\n<li>aus.<\/li>\n<\/ul>\n<hr \/>\n<h2>Ber\u00fccksichtigen Sie die Auswirkungen der verz\u00f6gerten Ausl\u00f6sung auf die St\u00f6rlichtbogenenergie<\/h2>\n<p>Interne Links &amp; zugeh\u00f6rige Ressourcen<\/p>\n<ul>\n<li><a href=\"https:\/\/test.viox.com\/de\/electrical-derating-temperature-altitude-grouping-factors\/\"><strong>Elektrische Leistungsreduzierung: Temperatur, H\u00f6he und Gruppierungsfaktoren<\/strong><\/a> F\u00fcr ein tieferes Verst\u00e4ndnis verwandter Schutzkonzepte erkunden Sie diese technischen VIOX-Leitf\u00e4den:<\/li>\n<li><a href=\"https:\/\/test.viox.com\/de\/ats-circuit-breaker-coordination-guide-icw-selectivity\/\"><strong>\u2013 Erfahren Sie, wie sich Umweltfaktoren auf die Nennstr\u00f6me und die Koordination von Leistungsschaltern auswirken<sub>cw<\/sub> ATS- &amp; Leistungsschalter-Koordinationsleitfaden: I<\/strong><\/a> &amp; Selektivit\u00e4t erkl\u00e4rt<\/li>\n<li><a href=\"https:\/\/test.viox.com\/de\/current-limiting-circuit-breaker-guide\/\"><strong>Current-Limiting Circuit-Breaker Guide: Schutz &amp; Specs<\/strong><\/a> \u2013 Detaillierte Analyse der Kategorie-A- vs. Kategorie-B-Koordination in automatischen Umschalteinrichtungen<sup>2<\/sup>\u2013 Tiefer Einblick in die Physik der elektromagnetischen Absto\u00dfung und die I<\/li>\n<li><a href=\"https:\/\/test.viox.com\/de\/types-of-circuit-breakers\/\"><strong>Arten von Schutzschaltern: Vollst\u00e4ndiger Klassifizierungsleitfaden<\/strong><\/a> t-Begrenzung<\/li>\n<li><a href=\"https:\/\/test.viox.com\/de\/commercial-ev-charging-protection-guide-acb-mccb-rcbo\/\"><strong>\u2013 Umfassender \u00dcberblick \u00fcber ACB-, MCCB-, MCB-Unterschiede und -Anwendungen<\/strong><\/a> Leitfaden zum Schutz von kommerziellen EV-Ladestationen: ACB, MCCB &amp; Typ B RCBOs<\/li>\n<\/ul>\n<hr \/>\n<h2>\u2013 Beispiel f\u00fcr eine reale Koordination mit Lastberechnungen<\/h2>\n<h3>FAQ: MCCB-Kurzzeitselektivit\u00e4t<\/h3>\n<p><strong>Ein<\/strong>F1: Kann ich anstelle eines ACBs einen MCCB als Haupteinspeisung verwenden?<sub>cw<\/sub> : M\u00f6glich, aber nicht empfehlenswert f\u00fcr Systeme, die eine vollst\u00e4ndige Selektivit\u00e4t erfordern. MCCBs fehlen deklarierte I<sub>n<\/sub>-Werte, sodass sie die Ausl\u00f6sung bei hohen Fehlerstr\u00f6men (&gt;10\u00d7 I.<\/p>\n<h3>) nicht zuverl\u00e4ssig verz\u00f6gern k\u00f6nnen, um eine nachgeschaltete Koordination zu gew\u00e4hrleisten. Verwenden Sie ACBs f\u00fcr Haupteinspeisungen in Industrieanlagen, in denen Selektivit\u00e4t entscheidend ist, oder \u00fcberpr\u00fcfen Sie die Koordinationsgrenzen mit Herstellertabellen f\u00fcr kommerzielle Anwendungen.<sub>n<\/sub>?<\/h3>\n<p><strong>Ein<\/strong>F2: Was passiert, wenn ich die Kurzzeitverz\u00f6gerung des MCCB auf 0,5 s einstelle, der Fehlerstrom aber 20\u00d7 I <strong>sofort<\/strong> betr\u00e4gt?<sub>n<\/sub>: Der Leistungsschalter l\u00f6st<sub>n<\/sub>\u00fcber die magnetische Ausl\u00f6sung aus und ignoriert die 0,5-Sekunden-Verz\u00f6gerungseinstellung. MCCB-Kurzzeitverz\u00f6gerungen funktionieren nur, wenn der Fehlerstrom zwischen dem Kurzzeit-Ansprechwert (z. B. 2-10\u00d7 I.<\/p>\n<h3>) und der unverz\u00f6gerten Schwelle (z. B. 12\u00d7 I<\/h3>\n<p><strong>Ein<\/strong>) bleibt. Oberhalb der unverz\u00f6gerten Ausl\u00f6sung \u00fcberschreibt das magnetische Element die elektronischen Einstellungen.<sub>p<\/sub> F3: Verwenden alle MCCBs eine Strombegrenzungstechnologie?<sup>2<\/sup>: Nein. Thermisch-magnetische MCCBs (feste Ausl\u00f6sung, keine Einstellbarkeit) verwenden typischerweise langsamere Bimetall-\u00dcberlastelemente und erreichen m\u00f6glicherweise keine echte Strombegrenzung. Elektronische MCCBs mit schnell wirkenden Kontakten und optimierten L\u00f6schkammern sind eher strombegrenzend (\u00fcberpr\u00fcfen Sie dies anhand der Durchlasskurven des Herstellers, die I.<\/p>\n<h3>und I<\/h3>\n<p><strong>Ein<\/strong>t-Werte unterhalb der voraussichtlichen Fehlerstrompegel zeigen).<\/p>\n<ul>\n<li>F4: Wie \u00fcberpr\u00fcfe ich die Selektivit\u00e4t zwischen zwei MCCBs?<sup>2<\/sup>: Verwenden Sie die Koordinationstabellen des Herstellers (nicht nur Zeit-Strom-Kennlinien). Die Tabellen ber\u00fccksichtigen:<\/li>\n<li>Durchlassenergie (I<\/li>\n<li>t) des nachgeschalteten Leistungsschalters<br \/>\nNichtausl\u00f6seschwelle des vorgeschalteten Leistungsschalters.<\/li>\n<\/ul>\n<h3>Strombegrenzende Effekte bei verschiedenen Fehlerstrompegeln<sub>n<\/sub>)?<\/h3>\n<p><strong>Ein<\/strong>Beispiel: Schneider Electric bietet detaillierte Selektivit\u00e4tstabellen in seinen Koordinationsleitf\u00e4den, die maximale Selektivit\u00e4tsgrenzen zeigen (z. B. \u201eSelektiv bis 15 kA\u201c zwischen bestimmten MCCB-Modellen).<sub>n<\/sub> F5: Warum haben motorbemessene MCCBs h\u00f6here unverz\u00f6gerte Einstellungen (13-14\u00d7 I<sub>n<\/sub>)?.<\/p>\n<hr \/>\n<h2>Fazit<\/h2>\n<p>: Um Fehlausl\u00f6sungen beim direkten Einschalten (DOL) des Motors zu verhindern. Untersuchungen zeigen, dass der Motoranlaufstrom den 12-13-fachen I<sub>cw<\/sub> f\u00fcr die erste Spitze erreichen kann. Motorbemessene MCCBs haben auch h\u00f6here Kontaktabsto\u00dfungsschwellen (&gt;14\u00d7 I <strong>), um sicherzustellen, dass die Kontakte w\u00e4hrend der Einschalttransienten nicht aufspringen, was zu unn\u00f6tigem Verschlei\u00df und potentiellem Verschwei\u00dfen beim Wiedereinschalten f\u00fchren w\u00fcrde.<\/strong><\/p>\n<p>Das scheinbare Paradoxon, dass MCCBs einen Kurzzeitschutz ohne Nennwerte f\u00fcr I<sub>n<\/sub>bieten, beruht auf einem grundlegenden Unterschied in der Schutzphilosophie:.<\/p>\n<p><strong>ACBs widerstehen Fehlern durch mechanische Festigkeit und thermische Masse, w\u00e4hrend MCCBs Fehler durch elektromagnetische Physik und schnelle Lichtbogenunterbrechung begrenzen.<\/strong>Das Verst\u00e4ndnis dieses Unterschieds ist entscheidend f\u00fcr Elektroingenieure, die Koordinationsschemata entwerfen. MCCBs k\u00f6nnen eine selektive Koordination mit nachgeschalteten Ger\u00e4ten innerhalb ihrer inh\u00e4renten Kurzzeitfestigkeit (typischerweise 12-14\u00d7 I\u201c<\/p>\n<hr \/>\n<p><strong>\u00dcber VIOX Electric<\/strong>) erreichen, aber sie k\u00f6nnen das ACB-Verhalten bei hohen Fehlerstr\u00f6men, die sich ihrer Schaltleistung n\u00e4hern, nicht replizieren. F\u00fcr Anwendungen, die eine vollst\u00e4ndige Selektivit\u00e4t \u00fcber den gesamten Fehlerstrombereich erfordern, bleiben ACB-Haupteinspeisungen, die mit MCCB-Abg\u00e4ngen koordiniert sind, der Goldstandard \u2013 wobei die Kategorie-B-Zeitverz\u00f6gerungsfunktionen stromaufw\u00e4rts genutzt werden, w\u00e4hrend die Kategorie-A-Strombegrenzungsvorteile stromabw\u00e4rts genutzt werden. <a href=\"https:\/\/test.viox.com\/de\/\">Kontakt<\/a> Wichtiges Designprinzip.<\/p>\n<\/div>","protected":false},"excerpt":{"rendered":"<p>MCCB electronic trip unit in industrial panel showing 400A rating and current display &#8211; VIOX Electric Direct Answer Molded Case Circuit Breakers (MCCBs) can provide short-time delay protection without a rated short-time withstand current (Icw) because they belong to IEC 60947-2 Category A, where selectivity is achieved through current-limiting technology rather than intentional time delays. [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":21475,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"inline_featured_image":false,"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"footnotes":""},"categories":[1],"tags":[],"class_list":["post-21474","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog"],"_links":{"self":[{"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/posts\/21474","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/comments?post=21474"}],"version-history":[{"count":1,"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/posts\/21474\/revisions"}],"predecessor-version":[{"id":21476,"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/posts\/21474\/revisions\/21476"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/media\/21475"}],"wp:attachment":[{"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/media?parent=21474"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/categories?post=21474"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/test.viox.com\/de\/wp-json\/wp\/v2\/tags?post=21474"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}